Boilers and Water Heaters

Boilers and Water Heaters

This chapter establishes the installation and safety requirements for boilers, water heaters, and pool heaters, including controls, expansion tanks, and manufacturer instructions.

M2001 — Boilers

M200l.l Installation. In addition to the requirements of this code, the installation of boilers shall conform to the manufacturer's instructions. The manufacturer's rating data, the name-plate and operating instructions of a permanent type shall be attached to the boiler. Boilers shall have all controls set, adjusted and tested by the installer. A complete control diagram together with complete boiler operating instructions shall be furnished by the installer. Solid- and liquid-fuel-burning boilers shall be provided with combustion air as required by Chapter 17.

M200l.l.l Standards. Oil-fired boilers and their control systems shall be listed and labeled in accordance with UL 726. Electric boilers and their control systems shall be listed in accordance with UL 834. Boilers shall be designed and constructed in accordance with the requirements of ASME CSD-l and as applicable, the ASME Boiler and Pressure Vessel Code, Sections I and IV. Gas-fired boilers shall conform to the requirements listed in Chapter 24.

M200l.l.l Standards. Oil-fired boilers and their control systems shall be listed and labeled in accordance with UL 726. Electric boilers and their control systems shall be listed in accordance with UL 834. Boilers shall be designed and constructed in accordance with the requirements of ASME CSD-l and as applicable, the ASME Boiler and Pressure Vessel Code, Sections I and IV. Gas-fired boilers shall conform to the requirements listed in Chapter 24.

M200l.2 Clearance. Boilers shall be installed in accordance with their listing and label.

M200l.3 Valves. Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple boiler or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in the supply and return piping.

Exception: Shutoff valves are not required in a system having a single low-pressure steam boiler.

Exception: Shutoff valves are not required in a system having a single low-pressure steam boiler.

M200l.4 Flood-resistant installation. In areas prone to flooding as established in Table R30 1.2 (1), boilers, water heaters and their control systems shall be located or installed in accordance with Section R322.1.6.

Worked example

Scenario: An architect is designing a new residential project that includes a hydronic heating system. They are specifying the boiler for the system.

Explanation: According to M2001.1, the architect must ensure the boiler's installation conforms to the manufacturer's instructions. They also need to verify that the manufacturer's rating data, name-plate, and operating instructions will be permanently attached to the boiler upon installation.

M2002 — Operating and Safety Controls

M2002.l Safety controls. Electrical and mechanical operating and safety controls for boilers shall be listed and labeled.

M2002.2 Hot water boiler gauges. Every hot water boiler shall have a pressure gauge and a temperature gauge, or combination pressure and temperature gauge. The gauges shall indicate the temperature and pressure within the normal range of the system's operation.

M2002.3 Steam boiler gauges. Every steam boiler shall have a water-gauge glass and a pressure gauge. The pressure gauge shall indicate the pressure within the normal range of the system's operation. The gauge glass shall be installed so that the midpoint is at the normal water level.

M2002.4 Pressure-relief valve. Boilers shall be equipped with pressure-relief valves with minimum rated capacities for the equipment served. Pressure-relief valves shall be set at the maximum rating of the boiler. Discharge shall be piped to drains by gravity to within 18 inches (457 mm) of the floor or to an open receptor.

M2002.5 Boiler low-water cutoff. All steam and hot water boilers shall be protected with a low-water cutoff control. The low-water cutoffshall automatically stop the combustion operation of the appliance when the water level drops below the lowest safe water level as established by the manufacturer.

Worked example

Scenario: A designer is selecting the controls for a new boiler installation, including thermostats, high-limit switches, and pressure relief valves.

Explanation: Section M2002.1 mandates that all electrical and mechanical operating and safety controls for the boiler must be listed and labeled by a recognized testing agency to ensure they meet safety and performance standards.

M2003 — Expansion Tanks

M2003.l General. Hot water boilers shall be provided with expansion tanks. Nonpressurized expansion tanks shall be securely fastened to the structure or boiler and supported to carry twice the weight of the tank filled with water. Provisions shall be made for draining nonpressurized tanks without emptying the system.

M2003.l.l Pressurized expansion tanks. Pressurized expansion tanks shall be consistent with the volume and capacity of the system. Tanks shall be capable of withstanding a hydrostatic test pressure of two and one-half times the allowable working pressure of the system.

M2003.l.l Pressurized expansion tanks. Pressurized expansion tanks shall be consistent with the volume and capacity of the system. Tanks shall be capable of withstanding a hydrostatic test pressure of two and one-half times the allowable working pressure of the system.

M2003.2 Minimum capacity. The minimum capacity of expansion tanks shall be determined from Table M2003.2.

Worked example

Scenario: An engineer is designing a hot water boiler system for a residential building and needs to specify the expansion tank.

Explanation: Based on M2003.1, the design must include an expansion tank for the hot water boiler. If a nonpressurized tank is chosen, it must be securely fastened to the structure or boiler and supported to handle twice the weight of the tank when full of water. The design must also allow for draining the tank without emptying the entire system.

M2004 — Water Heaters Used for Space Heating

M2004.l General. Water heaters used to supply both potable hot water and hot water for space heating shall be installed in accordance with this chapter, Chapter 24, Chapter 28 and the manufacturer's installation instructions.

Worked example

Scenario: A homeowner wants to use a single water heater to provide hot water for both bathing and a radiant floor heating system in their new home.

Explanation: Per M2004.1, this dual-purpose setup is permitted but requires the water heater to be installed strictly in accordance with Chapter 20 (Boilers and Water Heaters), Chapter 24 (Fuel Gas), Chapter 28 (Potable Water), and the manufacturer's specific installation instructions for such applications.

M2005 — Water Heaters

M2005.l General. Water heaters shall be installed in accordance with the manufacturer's installation instructions and the requirements ofthis code. Water heaters installed in an atticshall conform to the requirements of Section MI305.1.3. Gas-fired water heaters shall conform to the requirements in Chapter 24. Domestic electric water heaters shall conform to UL 174 or UL 1453. Commercial electric water heaters shall conform to UL 1453. Oiled-fired water heaters shall conform to UL 732.

M2005.2 Prohibited locations. Fuel-fired water heaters shall not be installed in a room used as a storage closet. Water heaters located in a bedroom or bathroom shall be installed in a sealed enclosure so that combustion airwill not be taken from the living space. Installation of direct-vent water heaters within an enclosure is not required.

A table appears here in the adopted code. Refer to the official source for the full table.

M2005.2.1 Water heater access. Access to water heaters that are located in an attic or underfloor crawl space is permitted to be through a closet located in a sleeping room or bathroom where ventilation of those spaces is in accordance with this code.

M2005.2.1 Water heater access. Access to water heaters that are located in an attic or underfloor crawl space is permitted to be through a closet located in a sleeping room or bathroom where ventilation of those spaces is in accordance with this code.

M2005.3 Electric water heaters. Electric water heaters shall also be installed in accordance with the applicable provisions of Chapters 34 through 43.

M2005.4 Supplemental water-heating devices. Potable water heating devices that use refrigerant-to-water heat exchangers shall be approved and installed in accordance with the manufacturer's installation instructions.

Worked example

Scenario: An architect is planning the location for a new residential water heater, considering both basement and attic options.

Explanation: According to M2005.1, the water heater must be installed per the manufacturer's instructions and code requirements. If the water heater is placed in an attic, specific additional requirements outlined in Section M1305.1.3, likely related to drainage and access, must also be met. Gas-fired units also need to comply with Chapter 24.

M2006 — Pool Heaters

M2006.1 General. Pool and spa heaters shall be installed in accordance with the manufacturer's installation instructions. Oil-fired pool heaters shall be tested in accordance with UL 726. Electric pool and spa heaters shall be tested in accordance UL 1261.

M2006.2 Clearances. In no case shall the clearances interfere with combustion air, draft hood or flue terminal relief, or accessibility for servicing.

M2006.3 Temperature-limiting devices. Pool heaters shall have temperature-relief valves.

M2006.4 Bypass valves. Where an integral bypass system is not provided as a part ofthe pool heater, a bypass line and valve shall be installed between the inlet and outlet piping for use in adjusting the flow of water through the heater.

Worked example

Scenario: A landscape architect is specifying an electric heater for a new residential swimming pool and spa.

Explanation: Section M2006.1 requires the pool and spa heater to be installed according to the manufacturer's instructions. Additionally, if it's an electric pool and spa heater, it must be tested in accordance with UL 1261 to ensure safety and performance.

Frequently asked questions

What are the general installation requirements for boilers?

Boilers must be installed according to manufacturer's instructions, local code, and have permanent rating data, name-plate, and operating instructions attached, with controls properly set and adjusted.

Are expansion tanks required for hot water boilers?

Yes, hot water boilers must have expansion tanks. Nonpressurized tanks need to be securely fastened to the structure or boiler and supported to hold twice their water-filled weight, with provisions for draining without emptying the system.

Can a single water heater be used for both potable hot water and space heating?

Yes, a single water heater can serve both purposes, provided it is installed in compliance with this chapter, Chapter 24, Chapter 28, and the manufacturer's specific instructions.

Where verbatim source text is shown, it is reproduced from the code as adopted into law by the jurisdiction, sourced from public.resource.org under the government edicts doctrine (see Georgia v. Public.Resource.Org, Inc., 590 U.S. 255 (2020)). This material reflects enacted law and is provided for reference and educational purposes only. It is not legal advice and may not reflect local amendments or the most recently adopted edition. Always verify requirements with the authority having jurisdiction.