Floors
Floors
This chapter establishes the design and construction requirements for floors in all buildings, including those in attic spaces used for mechanical or plumbing equipment.
R501 — General
R501.1 Application. The provisions of this chapter shall control the design and construction of the floors for all buildings including the floors of atticspaces used to house mechanical or plumbing fixtures and equipment.
R501.2 Requirements. Floor construction shall be capable of accommodating all loads according to Section R301 and of transmitting the resulting loads to the supporting structural elements.
R502 — Wood Floor Framing
R502.1 Identification. Load-bearing dimension lumber for joists, beams and girders shall be identified by a grade mark of a lumber grading or inspection agency that has been approved by an accreditation body that complies with DOC PS 20. In lieu of a grade mark, a certificate of inspection issued by a lumber grading or inspection agency meeting the requirements of this section shall be accepted.
R502.1.1 Preservative-treated lumber. Preservative treated dimension lumber shall also be identified as required by Section R319.1. R502.1.2 Blocking and subflooring. Blocking shall be a minimum ofutility grade lumber. Subflooring may be a minimum ofutility grade lumber or No.4 common grade boards. R502.1.3 End-jointed lumber. Approvedend-jointed lumber identified by a grade mark conforming to Section R502.1 may be used interchangeably with solid-sawn members of the same species and grade. R502.1.4 Prefabricated wood I-joists. Structural capacities and design provisions for prefabricated wood I-joists shall be established and monitored in accordance with ASTMD 5055. R502.1.5 Structural glued laminated timbers. Glued laminated timbers shall be manufactured and identified as required in ANSI/AITC A190.1 and ASTM D 3737. R502.1.6 Structural log members. Stress grading ofstructural log members of nonrectangular shape, as typically used in log buildings, shall be in accordance with ASTM D 3957. Such structural log members shall be identified by the grade mark of an approved lumber grading or inspection agency. In lieu of a grade mark on the material, a certificate of inspection as to species and grade issued by a lumber-grading or inspection agency meeting the requirements of this section shall be permitted to be accepted. IR502.1.7 Exterior wood/plastic composite deck boards. Wood/plastic composites used in exterior deck boards shall comply with the provisions of Section R317.4.
R502.1.1 Preservative-treated lumber. Preservative treated dimension lumber shall also be identified as required by Section R319.1.
R502.1.2 Blocking and subflooring. Blocking shall be a minimum ofutility grade lumber. Subflooring may be a minimum ofutility grade lumber or No.4 common grade boards.
R502.1.3 End-jointed lumber. Approvedend-jointed lumber identified by a grade mark conforming to Section R502.1 may be used interchangeably with solid-sawn members of the same species and grade.
R502.1.4 Prefabricated wood I-joists. Structural capacities and design provisions for prefabricated wood I-joists shall be established and monitored in accordance with ASTMD 5055.
R502.1.5 Structural glued laminated timbers. Glued laminated timbers shall be manufactured and identified as required in ANSI/AITC A190.1 and ASTM D 3737.
R502.1.6 Structural log members. Stress grading ofstructural log members of nonrectangular shape, as typically used in log buildings, shall be in accordance with ASTM D 3957. Such structural log members shall be identified by the grade mark of an approved lumber grading or inspection agency. In lieu of a grade mark on the material, a certificate of inspection as to species and grade issued by a lumber-grading or inspection agency meeting the requirements of this section shall be permitted to be accepted.
IR502.1.7 Exterior wood/plastic composite deck boards. Wood/plastic composites used in exterior deck boards shall comply with the provisions of Section R317.4.
R502.2 Design and construction. Floors shall be designed and constructed in accordance with the provisions of this chapter, Figure R502.2 and Sections R317 and R318 or in accordance with AF&PA/NDS.
R502.2.1 Framing at braced wall lines. A load path for lateral forces shall be provided between floor framing and braced wallpanels located above or below a floor, as specified in Section R602.1 0.6. R502.2.2 Decks. Where supported by attachment to an exterior wall, decks shall be positively anchored to the primary structure and designed for both vertical and lateral loads as applicable. Such attachment shall not be accomplished by the use of toenails or nails subject to withdrawal. Where positive connection to the primary building structure cannot be verified during inspection, decks shall be self- supporting. For decks with cantilevered framing members, connections to exterior walls or other framing members, shall be designed and constructed to resist uplift resulting from the full live load specified in Table R301.5 acting on the cantilevered portion ofthe deck. R502.2.2.1 Deck ledger connection to band joist. For decks supporting a total design load of 50 pounds per square foot (2394 Pa) [40 pounds per square foot (1915 Pa) live load plus 10 pounds per square foot (479 Pa) dead load], the connection between a deck ledger of pressure-preservative-treated Southern Pine, incised pressure-preservative-treated Hem-Fir or approved decay- resistant species, and a 2-inch (51 mm) nominal lumber bandjoist bearing on a sill plate or wall plate shall be constructed with ½-inch (12.7 m) lag screws or bolts with washers in accordance with Table R502.2.2.1. Lag screws, bolts and washers shall be hot-dipped galvanized or stainless steel. R502.2.2.1.1 Placement of lag screws or bolts in deck ledgers. The lag screws or bolts shall be placed 2 inches (51 mm) in from the bottom or top ofthe deck ledgers and between 2 and 5 inches (51 and 127 mm) in from the ends. The lag screws or bolts shall be staggered from the top to the bottom along the horizontal run of the deck ledger. R502.2.2.2 Alternate deck ledger connections. Deck ledger connections not conforming to Table R502.2.2.1 shall be designed in accordance with accepted engineering practice. Girders supporting deck joists shall not be supported on deck ledgers or band joists. Deck ledgers shall not be supported on stone or masonry veneer. R502.2.2.3 Deck lateral load connection. The lateral load connection required by Section R502.2.2 shall be permitted to be in accordance with Figure R502.2.2.3. Hold-down tension devices shall be installed in not less than two locations per deck, and each device shall have an allowable stress design capacity of not less than 1500 pounds (6672 N). R502.2.2.4 Exterior wood/plastic composite deck boards. Wood/plastic composite deck boards shall be installed in accordance with the manufacturer's instructions.
R502.2.1 Framing at braced wall lines. A load path for lateral forces shall be provided between floor framing and braced wallpanels located above or below a floor, as specified in Section R602.1 0.6.
R502.2.2 Decks. Where supported by attachment to an exterior wall, decks shall be positively anchored to the primary structure and designed for both vertical and lateral loads as applicable. Such attachment shall not be accomplished by the use of toenails or nails subject to withdrawal. Where positive connection to the primary building structure cannot be verified during inspection, decks shall be self- supporting. For decks with cantilevered framing members, connections to exterior walls or other framing members, shall be designed and constructed to resist uplift resulting from the full live load specified in Table R301.5 acting on the cantilevered portion ofthe deck.
R502.2.2.1 Deck ledger connection to band joist. For decks supporting a total design load of 50 pounds per square foot (2394 Pa) [40 pounds per square foot (1915 Pa) live load plus 10 pounds per square foot (479 Pa) dead load], the connection between a deck ledger of pressure-preservative-treated Southern Pine, incised pressure-preservative-treated Hem-Fir or approved decay- resistant species, and a 2-inch (51 mm) nominal lumber bandjoist bearing on a sill plate or wall plate shall be constructed with ½-inch (12.7 m) lag screws or bolts with washers in accordance with Table R502.2.2.1. Lag screws, bolts and washers shall be hot-dipped galvanized or stainless steel. R502.2.2.1.1 Placement of lag screws or bolts in deck ledgers. The lag screws or bolts shall be placed 2 inches (51 mm) in from the bottom or top ofthe deck ledgers and between 2 and 5 inches (51 and 127 mm) in from the ends. The lag screws or bolts shall be staggered from the top to the bottom along the horizontal run of the deck ledger. R502.2.2.2 Alternate deck ledger connections. Deck ledger connections not conforming to Table R502.2.2.1 shall be designed in accordance with accepted engineering practice. Girders supporting deck joists shall not be supported on deck ledgers or band joists. Deck ledgers shall not be supported on stone or masonry veneer. R502.2.2.3 Deck lateral load connection. The lateral load connection required by Section R502.2.2 shall be permitted to be in accordance with Figure R502.2.2.3. Hold-down tension devices shall be installed in not less than two locations per deck, and each device shall have an allowable stress design capacity of not less than 1500 pounds (6672 N). R502.2.2.4 Exterior wood/plastic composite deck boards. Wood/plastic composite deck boards shall be installed in accordance with the manufacturer's instructions.
R502.2.2.1 Deck ledger connection to band joist. For decks supporting a total design load of 50 pounds per square foot (2394 Pa) [40 pounds per square foot (1915 Pa) live load plus 10 pounds per square foot (479 Pa) dead load], the connection between a deck ledger of pressure-preservative-treated Southern Pine, incised pressure-preservative-treated Hem-Fir or approved decay- resistant species, and a 2-inch (51 mm) nominal lumber bandjoist bearing on a sill plate or wall plate shall be constructed with ½-inch (12.7 m) lag screws or bolts with washers in accordance with Table R502.2.2.1. Lag screws, bolts and washers shall be hot-dipped galvanized or stainless steel.
R502.2.2.1.1 Placement of lag screws or bolts in deck ledgers. The lag screws or bolts shall be placed 2 inches (51 mm) in from the bottom or top ofthe deck ledgers and between 2 and 5 inches (51 and 127 mm) in from the ends. The lag screws or bolts shall be staggered from the top to the bottom along the horizontal run of the deck ledger.
R502.2.2.1.1 Placement of lag screws or bolts in deck ledgers. The lag screws or bolts shall be placed 2 inches (51 mm) in from the bottom or top ofthe deck ledgers and between 2 and 5 inches (51 and 127 mm) in from the ends. The lag screws or bolts shall be staggered from the top to the bottom along the horizontal run of the deck ledger.
R502.2.2.2 Alternate deck ledger connections. Deck ledger connections not conforming to Table R502.2.2.1 shall be designed in accordance with accepted engineering practice. Girders supporting deck joists shall not be supported on deck ledgers or band joists. Deck ledgers shall not be supported on stone or masonry veneer.
R502.2.2.3 Deck lateral load connection. The lateral load connection required by Section R502.2.2 shall be permitted to be in accordance with Figure R502.2.2.3. Hold-down tension devices shall be installed in not less than two locations per deck, and each device shall have an allowable stress design capacity of not less than 1500 pounds (6672 N).
R502.2.2.4 Exterior wood/plastic composite deck boards. Wood/plastic composite deck boards shall be installed in accordance with the manufacturer's instructions.
FIGURE RS02.2 FLOOR CONSTRUCTION
A table appears here in the adopted code. Refer to the official source for the full table.
FIGURE 502.2.2.3 DECK ATTACHMENT FOR LATERAL LOADS
R502.3 Allowablejoist spans. Spans for floor joists shall be in accordance with Tables R502 .3.1(1) and R502 .3.1(2). For other grades and species and for other loading conditions, refer to the AF&PA Span Tables for Joists and Rafters.
R502.3.1 Sleeping areas and attic joists. Table R502.3.1 (1) shall be used to determine the maximum allowable span of floor joists that support sleeping areas and attics that are accessed by means of a fixed stairway in accordance with Section R311.7 provided that the design live load does not exceed 30 pounds per square foot (1.44 kPa) and the design dead load does not exceed 20 pounds per square foot (0.96 kPa). The allowable span of ceiling joists that support attics used for limited storage or no storage shall be determined in accordance with Section R802.4. R502.3.2 Other floor joists. Table R502.3.1 (2) shall be used to determine the maximum allowable span of floor joists that support all other areas of the building, other than sleeping rooms and attics, provided that the design live load does not exceed 40 pounds per square foot (1.92 kPa) and the design dead load does not exceed 20 pounds per square foot (0.96 kPa). R502.3.3 Floor cantilevers. Floor cantilever spans shall not exceed the nominal depth of the wood floor joist. Floor cantilevers constructed in accordance with Table R502.3.3(1) shall be permitted when supporting alight-frame bearing wall and roof only. Floor cantilevers supporting an exterior balcony are permitted to be constructed in accordance with Table R502.3.3(2).
R502.3.1 Sleeping areas and attic joists. Table R502.3.1 (1) shall be used to determine the maximum allowable span of floor joists that support sleeping areas and attics that are accessed by means of a fixed stairway in accordance with Section R311.7 provided that the design live load does not exceed 30 pounds per square foot (1.44 kPa) and the design dead load does not exceed 20 pounds per square foot (0.96 kPa). The allowable span of ceiling joists that support attics used for limited storage or no storage shall be determined in accordance with Section R802.4.
R502.3.2 Other floor joists. Table R502.3.1 (2) shall be used to determine the maximum allowable span of floor joists that support all other areas of the building, other than sleeping rooms and attics, provided that the design live load does not exceed 40 pounds per square foot (1.92 kPa) and the design dead load does not exceed 20 pounds per square foot (0.96 kPa).
R502.3.3 Floor cantilevers. Floor cantilever spans shall not exceed the nominal depth of the wood floor joist. Floor cantilevers constructed in accordance with Table R502.3.3(1) shall be permitted when supporting alight-frame bearing wall and roof only. Floor cantilevers supporting an exterior balcony are permitted to be constructed in accordance with Table R502.3.3(2).
R502.4 Joists under bearing partitions. Joists under parallel bearing partitions shall be of adequate size to support the load. Doublejoists, sized to adequately support the load, that are separated to permit the installation of piping or vents shall be full depth solid blocked with lumber not less than 2 inches (51 mm) in nominal thickness spaced not more than 4 feet (1219 mm) on center. Bearing partitions perpendicular to joists shall not be offset from supporting girders, walls or partitions more than the joist depth unless such joists are of sufficient size to carry the additional load.
R502.5 Allowable girder spans. The allowable spans of girders fabricated of dimension lumber shall not exceed the values set forth in Tables R502.5(1) and R502.5(2).
R502.6 Bearing. The ends of each joist, beam or girder shall have not less than 1.5 inches (38 mm) of bearing on wood or metal and not less than 3 inches (76 mm) on masonry or concrete except where supported on a 1-inch-by-4-inch (25.4 mm by 102 mm) ribbon strip and nailed to the adjacent stud or by the use of approvedjoist hangers.
R502.6.1 Floor systems. Joists framing from opposite sides over a bearing support shall lap a minimum of 3 inches (76 mm) and shall be nailed together with a minimum three 1Od face nails. A wood or metal splice with strength equal to or greater than that provided by the nailed lap is permitted. R502.6.2 Joist framing. Joists framing into the side of a wood girder shall be supported by approved framing anchors or on ledger strips not less than nominal 2 inches by 2 inches (51 mm by 51 mm).
R502.6.1 Floor systems. Joists framing from opposite sides over a bearing support shall lap a minimum of 3 inches (76 mm) and shall be nailed together with a minimum three 1Od face nails. A wood or metal splice with strength equal to or greater than that provided by the nailed lap is permitted.
R502.6.2 Joist framing. Joists framing into the side of a wood girder shall be supported by approved framing anchors or on ledger strips not less than nominal 2 inches by 2 inches (51 mm by 51 mm).
R502.7 Lateral restraint at supports. Joists shall be supported laterally at the ends by full-depth solid blocking not less than 2 inches (51 mm) nominal in thickness; or by attachment to a full-depth header, band or rimjoist, or to an adjoining stud or shall be otherwise provided with lateral support to prevent rotation.
Exceptions: Trusses, structural composite lumber, structural glued-laminated members and I-joists shall be supported laterally as required by the manufacturer's recommendations. In Seismic Design Categories Do, D1 and Dz, lateral restraint shall also be provided at each intermediate support.
Exceptions:
- Trusses, structural composite lumber, structural glued-laminated members and I-joists shall be supported laterally as required by the manufacturer's recommendations.
- In Seismic Design Categories Do, D1 and Dz, lateral restraint shall also be provided at each intermediate support.
R502.7.1 Bridging. Joists exceeding a nominal 2 inches by 12 inches (51 mm by 305 mm) shall be supported laterally by solid blocking, diagonal bridging (wood or metal), or a continuous 1-inch-by-3-inch (25.4 mm by 76 mm) strip nailed across the bottom ofjoists perpendicular to joists at intervals not exceeding 8 feet (2438 mm).
Exception: Trusses, structural composite lumber, structural glued-laminated members and I-jOists shall be supported laterally as required by the manufacturer's recommendations.
Exception: Trusses, structural composite lumber, structural glued-laminated members and I-jOists shall be supported laterally as required by the manufacturer's recommendations.
R502.8 Drilling and notching. Structural floor members shall not be cut, bored or notched in excess of the limitations specified in this section. See Figure R502.8.
R502.8.1 Sawn lumber. Notches in solid lumberjoists, rafters and beams shall not exceed one-sixth of the depth of the member, shall not be longer than one-third of the depth of the member and shall not be located in the middle one-third of the span. Notches at the ends of the member shall not exceed one-fourth the depth of the member. The tension side of members 4 inches (102 mm) or greater in nominal thickness shall not be notched except at the ends of the members. The diameter of holes bored or cut into members shall not exceed one-third the depth of the member. Holes shall not be closer than 2 inches (51 mm) to the top or bottom of the member, or to any other hole located in the member. Where the member is also notched, the hole shall not be closer than 2 inches (51 mm) to the notch. R502.8.2 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, structural glue-laminated members or I-joists are prohibited except where permitted by the manufacturer's recommendations or where the effects of such alterations are specifically considered in the design of the member by a registered design professional.
R502.8.1 Sawn lumber. Notches in solid lumberjoists, rafters and beams shall not exceed one-sixth of the depth of the member, shall not be longer than one-third of the depth of the member and shall not be located in the middle one-third of the span. Notches at the ends of the member shall not exceed one-fourth the depth of the member. The tension side of members 4 inches (102 mm) or greater in nominal thickness shall not be notched except at the ends of the members. The diameter of holes bored or cut into members shall not exceed one-third the depth of the member. Holes shall not be closer than 2 inches (51 mm) to the top or bottom of the member, or to any other hole located in the member. Where the member is also notched, the hole shall not be closer than 2 inches (51 mm) to the notch.
R502.8.2 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, structural glue-laminated members or I-joists are prohibited except where permitted by the manufacturer's recommendations or where the effects of such alterations are specifically considered in the design of the member by a registered design professional.
R502.9 Fastening. Floor framing shall be nailed in accordance with Table R602. 3(1). Where posts and beam or girder construction is used to support floor framing, positive connections shall be provided to ensure against uplift and lateral displacement.
R502.10 Framing of openings. Openings in floor framing shall be framed with a header and trimmer joists. When the headerjoist span does not exceed 4 feet (1219 mm), the header joist may be a single member the same size as the floor joist. Single trimmerjoists may be used to carry a single headerjoist that is located within 3 feet (914 mm) of the trimmerjoist bearing. When the header joist span exceeds 4 feet (1219 mm), the trimmerjoists and the headerjoist shall be doubled and ofsufficient cross section to support the floor joists framing into the header. Approved hangers shall be used for the header joist to trimmerjoist connections when the headerjoist span exceeds 6 feet (1829 mm). Tailjoistsover 12 feet (3658 mm) long shall be supported at the header by framing anchors or on ledger strips not less than 2 inches by 2 inches (51 mm by 51 mm).
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
FIGURE R502.8 CUTTING, NOTCHING AND DRILLING
R502.11 Wood trusses.
R502.11.1 Design. Wood trusses shall be designed in accordance with approved engineering practice. The design and manufacture of metal plate connected wood trusses shall comply with ANSI/TPI 1. The truss design drawings shall be prepared by a registered professional where required by the statutes of the jurisdiction in which the project is to be constructed in accordance with Section RI06.1. R502.11.2 Bracing. Trusses shall be braced to prevent rotation and provide lateral stability in accordance with the requirements specified in the construction documents for the building and on the individual truss design drawings. In the absence of specific bracing requirements, trusses shall be braced in accordance with the Building Component Safety Information (BCSI 1-03) Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses. R502.11.3 Alterations to trusses. Truss members and components shall not be cut, notched, spliced or otherwise altered in any way without the approval ofa registered design professional. Alterations resulting in the addition of load (e.g., HVAC equipment, water heater, etc.), that exceed the design load for the truss, shall not be permitted without verification that the truss is capable ofsupporting the additional loading. R502.11.4 Truss design drawings. Truss design drawings, prepared in compliance with Section R502.11.1 , shall be submitted to the building official and approved prior to installation. Truss design drawings shall be provided with the shipment oftrusses delivered to thejob site. Truss design drawings shall include, at a minimum, the information specified below: Slope or depth, span and spacing. Location of all joints. Required bearing widths. Design loads as applicable: 4.1. Top chord live load;4.2. Top chord dead load;4.3. Bottom chord live load;4.4. Bottom chord dead load;4.5. Concentrated loads and their points of application; and4.6. Controlling wind and earthquake loads. Adjustments to lumber and joint connector design values for conditions of use. Each reaction force and direction. Joint connector type and description, e.g., size, thickness or gauge, and the dimensioned location of each joint connector except where symmetrically located relative to the joint interface. Lumber size, species and grade for each member. Connection requirements for: 9.1. Truss-to-girder-truss;9.2. Truss ply-to-ply; and9.3. Field splices. Calculated deflection ratio and/or maximum description for live and total load. Maximum axial compression forces in the truss members to enable the building designer to design the size, connections and anchorage of the permanent continuous lateral bracing. Forces shall be shown on the truss drawing or on supplemental documents. Required permanent truss member bracing location.
R502.11.1 Design. Wood trusses shall be designed in accordance with approved engineering practice. The design and manufacture of metal plate connected wood trusses shall comply with ANSI/TPI 1. The truss design drawings shall be prepared by a registered professional where required by the statutes of the jurisdiction in which the project is to be constructed in accordance with Section RI06.1.
R502.11.2 Bracing. Trusses shall be braced to prevent rotation and provide lateral stability in accordance with the requirements specified in the construction documents for the building and on the individual truss design drawings. In the absence of specific bracing requirements, trusses shall be braced in accordance with the Building Component Safety Information (BCSI 1-03) Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses.
R502.11.3 Alterations to trusses. Truss members and components shall not be cut, notched, spliced or otherwise altered in any way without the approval ofa registered design professional. Alterations resulting in the addition of load (e.g., HVAC equipment, water heater, etc.), that exceed the design load for the truss, shall not be permitted without verification that the truss is capable ofsupporting the additional loading.
R502.11.4 Truss design drawings. Truss design drawings, prepared in compliance with Section R502.11.1 , shall be submitted to the building official and approved prior to installation. Truss design drawings shall be provided with the shipment oftrusses delivered to thejob site. Truss design drawings shall include, at a minimum, the information specified below:
- Slope or depth, span and spacing.
- Location of all joints.
- Required bearing widths.
- Design loads as applicable: 4.1. Top chord live load;4.2. Top chord dead load;4.3. Bottom chord live load;4.4. Bottom chord dead load;4.5. Concentrated loads and their points of application; and4.6. Controlling wind and earthquake loads.
- Adjustments to lumber and joint connector design values for conditions of use.
- Each reaction force and direction.
- Joint connector type and description, e.g., size, thickness or gauge, and the dimensioned location of each joint connector except where symmetrically located relative to the joint interface.
- Lumber size, species and grade for each member.
- Connection requirements for: 9.1. Truss-to-girder-truss;9.2. Truss ply-to-ply; and9.3. Field splices.
- Calculated deflection ratio and/or maximum description for live and total load.
- Maximum axial compression forces in the truss members to enable the building designer to design the size, connections and anchorage of the permanent continuous lateral bracing. Forces shall be shown on the truss drawing or on supplemental documents.
- Required permanent truss member bracing location.
4.1. Top chord live load;4.2. Top chord dead load;4.3. Bottom chord live load;4.4. Bottom chord dead load;4.5. Concentrated loads and their points of application; and4.6. Controlling wind and earthquake loads.
4.1. Top chord live load;4.2. Top chord dead load;4.3. Bottom chord live load;4.4. Bottom chord dead load;4.5. Concentrated loads and their points of application; and4.6. Controlling wind and earthquake loads.
9.1. Truss-to-girder-truss;9.2. Truss ply-to-ply; and9.3. Field splices.
9.1. Truss-to-girder-truss;9.2. Truss ply-to-ply; and9.3. Field splices.
R502.12 Draftstopping required. Draftstopping shall be provided in accordance with Section R302.12.
R502.13 Fireblocking required. Fireblocking shall be provided in accordance with Section R302.11.

R503 — Floor Sheathing
R503.1 Lumber sheathing. Maximum allowable spans for lumber used as floor sheathing shall conform to Tables R503.1 , R503.2.1.1 (1) and R503.2.1.1 (2).
R503.1.1 End joints. End joints in lumber used as subflooring shall occur over supports unless end-matched lumber is used, in which case each piece shall bear on at least two joists. Subflooring may be omitted when joist spacing does not exceed 16 inches (406 mm) and a I-inch (25.4 mm) nominal tongue-and-groove wood strip flooring is applied perpendicular to the joists.
R503.1.1 End joints. End joints in lumber used as subflooring shall occur over supports unless end-matched lumber is used, in which case each piece shall bear on at least two joists. Subflooring may be omitted when joist spacing does not exceed 16 inches (406 mm) and a I-inch (25.4 mm) nominal tongue-and-groove wood strip flooring is applied perpendicular to the joists.
A table appears here in the adopted code. Refer to the official source for the full table.
R503.2 Wood structural panel sheathing.
R503.2.1 Identification and grade. Wood structural panel sheathing used for structural purposes shall conform to DOC PS 1, DOC PS 2 or, when manufactured in Canada, CSA 0437 or CSA 0325. All panels shall be identified by a grade mark of certificate or inspection issued by an approved agency. R503.2.1.1 Subfloor and combined subfloor underlayment. Where used as subflooring or combination subfloor underlayment, wood structural panels shall be of one of the grades specified in Table R503.2.1.1 (1). When sanded plywood is used as combination subfloor underlayment, the grade shall be as specified in Table R503.2.1.1 (2).
R503.2.1 Identification and grade. Wood structural panel sheathing used for structural purposes shall conform to DOC PS 1, DOC PS 2 or, when manufactured in Canada, CSA 0437 or CSA 0325. All panels shall be identified by a grade mark of certificate or inspection issued by an approved agency.
R503.2.1.1 Subfloor and combined subfloor underlayment. Where used as subflooring or combination subfloor underlayment, wood structural panels shall be of one of the grades specified in Table R503.2.1.1 (1). When sanded plywood is used as combination subfloor underlayment, the grade shall be as specified in Table R503.2.1.1 (2).
R503.2.1.1 Subfloor and combined subfloor underlayment. Where used as subflooring or combination subfloor underlayment, wood structural panels shall be of one of the grades specified in Table R503.2.1.1 (1). When sanded plywood is used as combination subfloor underlayment, the grade shall be as specified in Table R503.2.1.1 (2).
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
R503.2.2 Allowable spans. The maximum allowable span for wood structural panels used as subfloor or combination subfloor underlayment shall be as set forth in Table R503.2.1.1 (1), or APA E30. The maximum span for sanded plywood combination subfloor underlayment shall be as set forth in Table R503.2.1.1(2). R503.2.3 Installation. Wood structural panels used as subfloor or combination subfloor underlayment shall be attached to wood framing in accordance with Table R602.3(1) and shall be attached to cold-formed steel framing in accordance with Table R505.3.1 (2).
R503.2.2 Allowable spans. The maximum allowable span for wood structural panels used as subfloor or combination subfloor underlayment shall be as set forth in Table R503.2.1.1 (1), or APA E30. The maximum span for sanded plywood combination subfloor underlayment shall be as set forth in Table R503.2.1.1(2).
R503.2.3 Installation. Wood structural panels used as subfloor or combination subfloor underlayment shall be attached to wood framing in accordance with Table R602.3(1) and shall be attached to cold-formed steel framing in accordance with Table R505.3.1 (2).
R503.3 Particleboard.
R503.3.1 Identification and grade. Particleboard shall conform to ANSI A208.1 and shall be so identified by a grade mark or certificate of inspection issued by an approved agency. R503.3.2 Floor underlayment. Particleboard floor underlayment shall conform to Type PBU and shall not be less than ¼ inch (6.4 mm) in thickness. R503.3.3 Installation. Particleboard underlayment shall be installed in accordance with the recommendations of the manufacturer and attached to framing in accordance with Table R602.3(1).
R503.3.1 Identification and grade. Particleboard shall conform to ANSI A208.1 and shall be so identified by a grade mark or certificate of inspection issued by an approved agency.
R503.3.2 Floor underlayment. Particleboard floor underlayment shall conform to Type PBU and shall not be less than ¼ inch (6.4 mm) in thickness.
R503.3.3 Installation. Particleboard underlayment shall be installed in accordance with the recommendations of the manufacturer and attached to framing in accordance with Table R602.3(1).
R504 — Pressure Preservatively Treated-wood Floors (on Ground)
R504.1 General. Pressure preservatively treated-wood base-mentfloors and floors on ground shall be designed to withstand axial forces and bending moments resulting from lateral soil pressures at the base of the exterior walls and floor live and dead loads. Floor framing shall be designed to meet joist deflection requirements in accordance with Section R301.
R504.1.1 Unbalanced soil loads. Unless special provision is made to resist sliding caused by unbalanced lateral soil loads, wood basement floors shall be limited to applications where the differential depth of fill on opposite exterior foundation walls is 2 feet (610 mm) or less. R504.1.2 Construction. Joists in wood basement floors shall bear tightly against the narrow face of studs in the foundation wall or directly against a bandjoist that bears on the studs. Plywood subfloor shall be continuous over lapped joists or over butt joints between in-line joists. Sufficient blocking shall be provided betweenjoists to transfer lateral forces at the base of the end walls into the floor system. R504.1.3 Uplift and buckling. Where required, resistance to uplift or restraint against buckling shall be provided by interior bearing walls or properly designed stub walls anchored in the supporting soil below.
R504.1.1 Unbalanced soil loads. Unless special provision is made to resist sliding caused by unbalanced lateral soil loads, wood basement floors shall be limited to applications where the differential depth of fill on opposite exterior foundation walls is 2 feet (610 mm) or less.
R504.1.2 Construction. Joists in wood basement floors shall bear tightly against the narrow face of studs in the foundation wall or directly against a bandjoist that bears on the studs. Plywood subfloor shall be continuous over lapped joists or over butt joints between in-line joists. Sufficient blocking shall be provided betweenjoists to transfer lateral forces at the base of the end walls into the floor system.
R504.1.3 Uplift and buckling. Where required, resistance to uplift or restraint against buckling shall be provided by interior bearing walls or properly designed stub walls anchored in the supporting soil below.
R504.2 Site preparation. The area within the foundation walls shall have all vegetation, topsoil and foreign material removed, and any fill material that is added shall be free of vegetation and foreign material. The fill shall be compacted to assure uniform support of the pressure preservatively treated-wood floor sleepers.
R504.2.1 Base. A minimum 4-inch-thick (102 mm) granular base of gravel having a maximum size of ¾ inch (19.1mm) or crushed stone having a maximum size of ½ inch (12.7 mm) shall be placed over the compacted earth.
R504.2.1 Base. A minimum 4-inch-thick (102 mm) granular base of gravel having a maximum size of ¾ inch (19.1mm) or crushed stone having a maximum size of ½ inch (12.7 mm) shall be placed over the compacted earth.
R504.2.2 Moisture barrier. Polyethylene sheeting of minimum 6-mil (0.15 mm) thickness shall be placed over the granular base. Joints shall be lapped 6 inches (152 mm) and left unsealed. The polyethylene membrane shall be placed over the pressure preservatively treated-wood sleepers and shall not extend beneath the footing plates of the exterior walls.
R504.3 Materials. All framing materials, including sleepers, joists, blocking and plywood subflooring, shall be pressure-preservative treated and dried after treatment in accordance with AWPA U1 (Commodity Specification A, Use Category 4B and section 5.2), and shall bear the label of an accredited agency.
Worked example
Scenario: An architect is designing a new home with a pressure-preservatively treated wood basement floor that will be in contact with the ground.
Explanation: According to R504.1, the basement floor system must be designed to resist not only the standard floor live and dead loads but also the lateral soil pressures exerted against the exterior walls at the base. The floor framing must also meet joist deflection requirements.
R505 — Steel Floor Framing
R505.1 Cold-formed steel floor framing. Elements shall be straight and free of any defects that would significantly affect structural performance. Cold-formed steel floor framing members shall comply with the requirements of this section.
R505.1.1 Applicability limits. The provisions of this section shall control the construction ofcold-formed steel floor framing for buildings not greater than 60 feet (18 288 mm) in length perpendicular to thejoist span, not greater than 40 feet (12 192 mm) in width parallel to the joist span, and less than or equal to three stories above grade plane. Cold-formed steel floor framing constructed in accordance with the provisions of this section shall be limited to sites subjected to a maximum design wind speed of 110 miles per hour (49 m/s) , Exposure B or C, and a maximum ground snow load of 70 pounds per square foot (3.35 kPa). R505.1.2 In-line framing. When supported by cold-formed steel framed walls in accordance with Section R603, cold-formed steel floor framing shall be constructed with floor joists located in-line with load-bearing studs located below the joists in accordance with Figure R505.1.2 and the tolerances specified as follows: The maximum tolerance shall be ¾ inch (19.1 mm) between the centerline of the horizontal framing member and the centerline of the vertical framing member. Where the centerline of the horizontal framing member and bearing stiffener are located to one side of the centerline of the vertical framing member, the maximum tolerance shall be l/S inch (3 mm) between the web of the horizontal framing member and the edge of the vertical framing member. R505.1.3 Floor trusses. Cold-formed steel trusses shall be designed, braced and installed in accordance with AISI S100, Section D4. Truss members shall not be notched, cut or altered in any manner without an approved design.
R505.1.1 Applicability limits. The provisions of this section shall control the construction ofcold-formed steel floor framing for buildings not greater than 60 feet (18 288 mm) in length perpendicular to thejoist span, not greater than 40 feet (12 192 mm) in width parallel to the joist span, and less than or equal to three stories above grade plane. Cold-formed steel floor framing constructed in accordance with the provisions of this section shall be limited to sites subjected to a maximum design wind speed of 110 miles per hour (49 m/s) , Exposure B or C, and a maximum ground snow load of 70 pounds per square foot (3.35 kPa).
R505.1.2 In-line framing. When supported by cold-formed steel framed walls in accordance with Section R603, cold-formed steel floor framing shall be constructed with floor joists located in-line with load-bearing studs located
below the joists in accordance with Figure R505.1.2 and the tolerances specified as follows:
- The maximum tolerance shall be ¾ inch (19.1 mm) between the centerline of the horizontal framing member and the centerline of the vertical framing member.
- Where the centerline of the horizontal framing member and bearing stiffener are located to one side of the centerline of the vertical framing member, the maximum tolerance shall be l/S inch (3 mm) between the web of the horizontal framing member and the edge of the vertical framing member.
R505.1.3 Floor trusses. Cold-formed steel trusses shall be designed, braced and installed in accordance with AISI S100, Section D4. Truss members shall not be notched, cut or altered in any manner without an approved design.
R505.2 Structural framing. Load-bearing cold-formed steel floor framing members shall comply with Figure R505.2(1) and with the dimensional and minimum thickness requirements specified in Tables R505.2(1) and R505.2(2). Tracks shall comply with Figure R505.2(2) and shall have a minimum flange width of 1¼ inches (32 mm). The maximum inside bend radius for members shall be the greater of 3/32 inch (2.4 mm) minus half the base steel thickness or 1.5 times the base steel thickness.
R505.2.1 Material. Load-bearing cold-formed steel framing members shall be cold-formed to shape from structural quality sheet steel complying with the requirements of one of the following: ASTM A 653: Grades 33 and 50 (Class 1 and 3). ASTM A 792: Grades 33 and 50A. ASTM A 1003: Structural Grades 33 Type Hand 50 Type H. R505.2.2 Identification. Load-bearing cold-formed steel framing members shall have a legible label, stencil, stamp or embossment with the following information as a minimum: Manufacturer's identification. Minimum base steel thickness in inches (mm). Minimum coating designation. Minimum yield strength, in kips per square inch (ksi) (MPa). R505.2.3 Corrosion protection. Load-bearing cold-formed steel framing shall have a metallic coating complying with ASTM A 1003 and one of the following: A minimum of G 60 in accordance with ASTM A 653. A minimum of AZ 50 in accordance with ASTM A 792.
R505.2.1 Material. Load-bearing cold-formed steel framing members shall be cold-formed to shape from structural quality sheet steel complying with the requirements of one of the following:
- ASTM A 653: Grades 33 and 50 (Class 1 and 3).
- ASTM A 792: Grades 33 and 50A.
- ASTM A 1003: Structural Grades 33 Type Hand 50 Type H.
R505.2.2 Identification. Load-bearing cold-formed steel framing members shall have a legible label, stencil, stamp or embossment with the following information as a minimum:
- Manufacturer's identification.
- Minimum base steel thickness in inches (mm).
- Minimum coating designation.
- Minimum yield strength, in kips per square inch (ksi) (MPa).
R505.2.3 Corrosion protection. Load-bearing cold-formed steel framing shall have a metallic coating complying with ASTM A 1003 and one of the following:
- A minimum of G 60 in accordance with ASTM A 653.
- A minimum of AZ 50 in accordance with ASTM A 792.
FIGURE R505.1.2 IN-LINE FRAMING
FIGURE R505.2(1) C-SHAPED SECTION
FIGURE R505.2(2) TRACK SECTION
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
R505.2.4 Fastening requirements. Screws for steel-to-steel connections shall be installed with a minimum edge distance and center-to-center spacing of ½ inch (12.7 mm), shall be self-drilling tapping, and shall conform to ASTM C 1513. Floor sheathing shall be attached to cold-formed steel joists with minimum No. 8 self-drilling tapping screws that conform to ASTM C 1513. Screws attaching floor-sheathing to cold-formed steel joists shall have a minimum head diameter of 0.292 inch (7.4 mm) with countersunk heads and shall be installed with a minimum edge distance of ⅜ inch (9.5 mm). Gypsum board ceilings shall be attached to cold-formed steel joists with minimum No.6 screws conforming to ASTM C 954 or ASTM C 1513 with a bugle head style and shall be installed in accordance with Section R702. For all connections, screws shall extend through the steel a minimum of three exposed threads. All fasteners shall have rust inhibitive coating suitable for the installation in which they are being used, or be manufactured from material not susceptible to corrosion. Where No.8 screws are specified in a steel-to-steel connection, the required number of screws in the connection is permitted to be reduced in accordance with the reduction factors in Table R505.2.4 when larger screws are used or when one of the sheets of steel being connected is thicker than 33 mils (0.84 mm). When applying the reduction factor, the resulting number of screws shall be rounded up.
R505.2.4 Fastening requirements. Screws for steel-to-steel connections shall be installed with a minimum edge distance and center-to-center spacing of ½ inch (12.7 mm), shall be self-drilling tapping, and shall conform to ASTM C 1513. Floor sheathing shall be attached to cold-formed steel joists with minimum No. 8 self-drilling tapping screws that conform to ASTM C 1513. Screws attaching floor-sheathing to cold-formed steel joists shall have a minimum head diameter of 0.292 inch (7.4 mm) with countersunk heads and shall be installed with a minimum edge distance of ⅜ inch (9.5 mm). Gypsum board ceilings shall be attached to cold-formed steel joists with minimum No.6 screws conforming to ASTM C 954 or ASTM C 1513 with a bugle head style and shall be installed in accordance with Section R702. For all connections, screws shall extend through the steel a minimum of three exposed threads. All fasteners shall have rust inhibitive coating suitable for the installation in which they are being used, or be manufactured from material not susceptible to corrosion.
Where No.8 screws are specified in a steel-to-steel connection, the required number of screws in the connection is permitted to be reduced in accordance with the reduction factors in Table R505.2.4 when larger screws are used or when one of the sheets of steel being connected is thicker than 33 mils (0.84 mm). When applying the reduction factor, the resulting number of screws shall be rounded up.
A table appears here in the adopted code. Refer to the official source for the full table.
R505.2.5 Web holes, web hole reinforcing and web hole patching. Web holes, web hole reinforcing, and web hole patching shall be in accordance with this section. R505.2.5.1 Web holes. Web holes in floor joists shall comply with all of the following conditions: Holes shall conform to Figure R505.2.5.1; Holes shall be permitted only along the centerline of the web of the framing member; Holes shall have a center-to-center spacing of not less than 24 inches (610 mm); Holes shall have a web hole width not greater than 0.5 times the member depth, or 2½ inches (64.5 mm); Holes shall have a web hole length not exceeding 4½ inches (114 mm); and Holes shall have a minimum distance between the edge of the bearing surface and the edge of the web hole of not less than 10 inches (254 mm). Framing members with web holes not conforming to the above requirements shall be reinforced in accordance with Section R505.2.5.2, patched in accordance with Section R505.2.5.3 or designed in accordance with accepted engineering practices. R505.2.5.2 Web hole reinforcing. Reinforcement of web holes in floor joists not conforming to the requirements of Section R505.2.5.1 shall be permitted if the hole is located fully within the center 40 percent of the span and the depth and length of the hole does not exceed 65 percent of the flat width of the web. The reinforcing shall be a steel plate or C-shape section with a hole that does not exceed the web hole size limitations of Section R505.2.5.1 for the member being reinforced. The steel reinforcing shall be the same thickness as the receiving member and shall extend at least 1 inch (25.4 mm) beyond all edges of the hole. The steel reinforcing shall be fastened to the web of the receiving member with No.8 screws spaced no more than 1 inch (25.4 mm) center-to-center along the edges of the patch with minimum edge distance of ½ inch (12.7 mm).
R505.2.5 Web holes, web hole reinforcing and web hole patching. Web holes, web hole reinforcing, and web hole patching shall be in accordance with this section.
R505.2.5.1 Web holes. Web holes in floor joists shall comply with all of the following conditions: Holes shall conform to Figure R505.2.5.1; Holes shall be permitted only along the centerline of the web of the framing member; Holes shall have a center-to-center spacing of not less than 24 inches (610 mm); Holes shall have a web hole width not greater than 0.5 times the member depth, or 2½ inches (64.5 mm); Holes shall have a web hole length not exceeding 4½ inches (114 mm); and Holes shall have a minimum distance between the edge of the bearing surface and the edge of the web hole of not less than 10 inches (254 mm). Framing members with web holes not conforming to the above requirements shall be reinforced in accordance with Section R505.2.5.2, patched in accordance with Section R505.2.5.3 or designed in accordance with accepted engineering practices. R505.2.5.2 Web hole reinforcing. Reinforcement of web holes in floor joists not conforming to the requirements of Section R505.2.5.1 shall be permitted if the hole is located fully within the center 40 percent of the span and the depth and length of the hole does not exceed 65 percent of the flat width of the web. The reinforcing shall be a steel plate or C-shape section with a hole that does not exceed the web hole size limitations of Section R505.2.5.1 for the member being reinforced. The steel reinforcing shall be the same thickness as the receiving member and shall extend at least 1 inch (25.4 mm) beyond all edges of the hole. The steel reinforcing shall be fastened to the web of the receiving member with No.8 screws spaced no more than 1 inch (25.4 mm) center-to-center along the edges of the patch with minimum edge distance of ½ inch (12.7 mm).
R505.2.5.1 Web holes. Web holes in floor joists shall comply with all of the following conditions:
- Holes shall conform to Figure R505.2.5.1;
- Holes shall be permitted only along the centerline of the web of the framing member;
- Holes shall have a center-to-center spacing of not less than 24 inches (610 mm);
- Holes shall have a web hole width not greater than 0.5 times the member depth, or 2½ inches (64.5 mm);
- Holes shall have a web hole length not exceeding 4½ inches (114 mm); and
- Holes shall have a minimum distance between the edge of the bearing surface and the edge of the web hole of not less than 10 inches (254 mm).
Framing members with web holes not conforming to the above requirements shall be reinforced in accordance with Section R505.2.5.2, patched in accordance with Section R505.2.5.3 or designed in accordance with accepted engineering practices.
R505.2.5.2 Web hole reinforcing. Reinforcement of web holes in floor joists not conforming to the requirements of Section R505.2.5.1 shall be permitted if the hole is located fully within the center 40 percent of the span and the depth and length of the hole does not exceed 65 percent of the flat width of the web. The reinforcing shall be a steel plate or C-shape section with a hole that does not exceed the web hole size limitations of Section R505.2.5.1 for the member being reinforced. The steel reinforcing shall be the same thickness as the receiving member and shall extend at least 1 inch (25.4 mm) beyond all edges of the hole. The steel reinforcing shall be fastened to the web of the receiving member with No.8 screws spaced no more than 1 inch (25.4 mm) center-to-center along the edges of the patch with minimum edge distance of ½ inch (12.7 mm).
FIGURE R505.2.5.1 FLOOR JOIST WEB HOLES
R505.2.5.3 Hole patching. Patching of web holes in floor joists not conforming to the requirements in Section R505.2.5.1 shall be permitted in accordance with either of the following methods: Framing members shall be replaced or designed in accordance with accepted engineering practices where web holes exceed the following size limits: 1.1. The depth of the hole, measured across the web, exceeds 70 percent ofthe flat width of the web; or 1.2. The length of the hole measured along the web, exceeds 10 inches (254 mm) or the depth of the web, whichever is greater. Web holes not exceeding the dimensional requirements in Section R505.2.5.3, Item 1, shall be patched with a solid steel plate, stud section, or track section in accordance with Figure R505.2.5.3. The steel patch shall, as a minimum, be of the same thickness as the receiving member and shall extend at least 1 inch (25 mm) beyond all edges of the hole. The steel patch shall be fastened to the web of the receiving member with No.8 screws spaced no more than 1 inch (25 mm) center-to-center along the edges of the patch with minimum edge distance of ½ inch (13 mm).
R505.2.5.3 Hole patching. Patching of web holes in floor joists not conforming to the requirements in Section R505.2.5.1 shall be permitted in accordance with either of the following methods: Framing members shall be replaced or designed in accordance with accepted engineering practices where web holes exceed the following size limits: 1.1. The depth of the hole, measured across the web, exceeds 70 percent ofthe flat width of the web; or 1.2. The length of the hole measured along the web, exceeds 10 inches (254 mm) or the depth of the web, whichever is greater. Web holes not exceeding the dimensional requirements in Section R505.2.5.3, Item 1, shall be patched with a solid steel plate, stud section, or track section in accordance with Figure R505.2.5.3. The steel patch shall, as a minimum, be of the same thickness as the receiving member and shall extend at least 1 inch (25 mm) beyond all edges of the hole. The steel patch shall be fastened to the web of the receiving member with No.8 screws spaced no more than 1 inch (25 mm) center-to-center along the edges of the patch with minimum edge distance of ½ inch (13 mm).
R505.2.5.3 Hole patching. Patching of web holes in floor joists not conforming to the requirements in Section R505.2.5.1 shall be permitted in accordance with either of the following methods:
- Framing members shall be replaced or designed in accordance with accepted engineering practices where web holes exceed the following size limits: 1.1. The depth of the hole, measured across the web, exceeds 70 percent ofthe flat width of the web; or 1.2. The length of the hole measured along the web, exceeds 10 inches (254 mm) or the depth of the web, whichever is greater.
- Web holes not exceeding the dimensional requirements in Section R505.2.5.3, Item 1, shall be patched with a solid steel plate, stud section, or track section in accordance with Figure R505.2.5.3. The steel patch shall, as a minimum, be of the same thickness as the receiving member and shall extend at least 1 inch (25 mm) beyond all edges of the hole. The steel patch shall be fastened to the web of the receiving member with No.8 screws spaced no more than 1 inch (25 mm) center-to-center along the edges of the patch with minimum edge distance of ½ inch (13 mm).
1.1. The depth of the hole, measured across the web, exceeds 70 percent ofthe flat width of the web; or 1.2. The length of the hole measured along the web, exceeds 10 inches (254 mm) or the depth of the web, whichever is greater.
1.1. The depth of the hole, measured across the web, exceeds 70 percent ofthe flat width of the web; or
1.2. The length of the hole measured along the web, exceeds 10 inches (254 mm) or the depth of the web, whichever is greater.
R505.3 Floor construction. Cold-formed steel floors shall be constructed in accordance with this section.
R505.3.1 Floor to foundation or load-bearing wall connections. Cold-formed steel framed floors shall be anchored to foundations, wood sills or load-bearing walls in accordance with Table R505.3.1 (1) and Figure R505.3.1 (1), R505.3.1 (2), R505.3.1 (3), R505.3.1 (4), R505.3.1 (5) or R505.3.1 (6). Anchor bolts shall be located not more than 12 inches (305 mm) from corners or the termination of bottom
R505.3.1 Floor to foundation or load-bearing wall connections. Cold-formed steel framed floors shall be anchored to foundations, wood sills or load-bearing walls in accordance with Table R505.3.1 (1) and Figure R505.3.1 (1), R505.3.1 (2), R505.3.1 (3), R505.3.1 (4), R505.3.1 (5) or R505.3.1 (6). Anchor bolts shall be located not more than 12 inches (305 mm) from corners or the termination of bottom
FIGURE R505.2.5.3 WEB HOLE PATCH
tracks. Continuous cold-formed steel joists supported by interior load-bearing walls shall be constructed in accordance with Figure R505.3.1 (7). Lapped cold-formed steel joists shall be constructed in accordance with Figure R505.3.1 (8). End floor joists constructed on foundation walls parallel to the joist span shall be doubled unless a C-shaped bearing stiffener, sized in accordance with Section R505.3.4, is installed web-to-web with the floor joist beneath each supported wall stud, as shown in Figure R505.3.1 (9). Fastening of cold-formed steeljoists to other framing members shall be in accordance with Section R505.2.4 and Table R505.3.1 (2). R505.3.2 Minimum floor joist sizes. Floor joist size and thickness shall be determined in accordance with the limits set forth in Table R505.3.2(1) for single spans, and Tables R505.3.2 (2) and R505.3.2 (3) for multiple spans. When continuous joist members are used, the interior bearing supports shall be located within 2 feet (610 mm) of mid-span of the cold-formed steel joists, and the individual spans shall not exceed the spans in Table R505.3.2(2) or R505.3.2(3), as applicable. Floor joists shall have a bearing support length of not less than 1½ inches (38 mm) for exterior wall supports and 3½ inches (89 mm) for interior wall supports. Tracks shall be a minimum of 33 mils (0.84 mm) thick except when used as part of a floor header or trimmer in accordance with Section R505.3.8. Bearing stiffeners shall be installed in accordance with Section R505.3.4. R505.3.3 joist bracing and blocking. Joist bracing and blocking shall be in accordance with this section. R505.3.3.1 joist top flange bracing. The top flanges of cold-formed steel joists shall be laterally braced by the application of floor sheathing fastened to the joists in accordance with Section R505. 2.4 and Table R505.3.1 (2). R505.3.3.2 joist bottom flange bracing/blocking. Floor joists with spans that exceed 12 feet (3658 mm) shall have the bottom flanges laterally braced in accordance with one of the following: Gypsum board installed with minimum No.6 screws in accordance with Section R702. Continuous steel straps installed in accordance with Figure R505.3.3.2(1). Steel straps shall be spaced at a maximum of 12 feet (3658 mm) on center and shall be at least 1½ inches (38 mm) in width and 33 mils (0.84 mm) in thickness. Straps shall be fastened to the bottom flange of eachjoist with one No.8 screw, fastened to blocking with two No.8 screws, and fastened at each end (of strap) with two No.8 screws. Blocking in accordance with Figure R505.3.3.2 (1) or Figure R505.3.3.2 (2) shall be installed between joists at each end of the continuous strapping and at a maximum spacing of 12 feet (3658 mm) measured along the continuous strapping (perpendicular to thejoist run). Blocking shall also be located at the termination of all straps. As an alternative to blocking at the ends, anchoring the strap to a stable building component with two No.8 screws shall be permitted.
tracks. Continuous cold-formed steel joists supported by interior load-bearing walls shall be constructed in accordance with Figure R505.3.1 (7). Lapped cold-formed steel joists shall be constructed in accordance with Figure R505.3.1 (8). End floor joists constructed on foundation walls parallel to the joist span shall be doubled unless a C-shaped bearing stiffener, sized in accordance with Section R505.3.4, is installed web-to-web with the floor joist beneath each supported wall stud, as shown in Figure R505.3.1 (9). Fastening of cold-formed steeljoists to other framing members shall be in accordance with Section R505.2.4 and Table R505.3.1 (2).
R505.3.2 Minimum floor joist sizes. Floor joist size and thickness shall be determined in accordance with the limits set forth in Table R505.3.2(1) for single spans, and Tables R505.3.2 (2) and R505.3.2 (3) for multiple spans. When continuous joist members are used, the interior bearing supports shall be located within 2 feet (610 mm) of mid-span of the cold-formed steel joists, and the individual spans shall not exceed the spans in Table R505.3.2(2) or R505.3.2(3), as applicable. Floor joists shall have a bearing support length of not less than 1½ inches (38 mm) for exterior wall supports and 3½ inches (89 mm) for interior wall supports. Tracks shall be a minimum of 33 mils (0.84 mm) thick except when used as part of a floor header or trimmer in accordance with Section R505.3.8. Bearing stiffeners shall be installed in accordance with Section R505.3.4.
R505.3.3 joist bracing and blocking. Joist bracing and blocking shall be in accordance with this section.
R505.3.3.1 joist top flange bracing. The top flanges of cold-formed steel joists shall be laterally braced by the application of floor sheathing fastened to the joists in accordance with Section R505. 2.4 and Table R505.3.1 (2). R505.3.3.2 joist bottom flange bracing/blocking. Floor joists with spans that exceed 12 feet (3658 mm) shall have the bottom flanges laterally braced in accordance with one of the following: Gypsum board installed with minimum No.6 screws in accordance with Section R702. Continuous steel straps installed in accordance with Figure R505.3.3.2(1). Steel straps shall be spaced at a maximum of 12 feet (3658 mm) on center and shall be at least 1½ inches (38 mm) in width and 33 mils (0.84 mm) in thickness. Straps shall be fastened to the bottom flange of eachjoist with one No.8 screw, fastened to blocking with two No.8 screws, and fastened at each end (of strap) with two No.8 screws. Blocking in accordance with Figure R505.3.3.2 (1) or Figure R505.3.3.2 (2) shall be installed between joists at each end of the continuous strapping and at a maximum spacing of 12 feet (3658 mm) measured along the continuous strapping (perpendicular to thejoist run). Blocking shall also be located at the termination of all straps. As an alternative to blocking at the ends, anchoring the strap to a stable building component with two No.8 screws shall be permitted.
R505.3.3.1 joist top flange bracing. The top flanges of cold-formed steel joists shall be laterally braced by the application of floor sheathing fastened to the joists in accordance with Section R505. 2.4 and Table R505.3.1 (2).
R505.3.3.2 joist bottom flange bracing/blocking. Floor joists with spans that exceed 12 feet (3658 mm) shall have the bottom flanges laterally braced in accordance with one of the following:
- Gypsum board installed with minimum No.6 screws in accordance with Section R702.
- Continuous steel straps installed in accordance with Figure R505.3.3.2(1). Steel straps shall be spaced at a maximum of 12 feet (3658 mm) on center and shall be at least 1½ inches (38 mm) in width and 33 mils (0.84 mm) in thickness. Straps shall be fastened to the bottom flange of eachjoist with one No.8 screw, fastened to blocking with two No.8 screws, and fastened at each end (of strap) with two No.8 screws. Blocking in accordance with Figure R505.3.3.2 (1) or Figure R505.3.3.2 (2) shall be installed between joists at each end of the continuous strapping and at a maximum spacing of 12 feet (3658 mm) measured along the continuous strapping (perpendicular to thejoist run). Blocking shall also be located at the termination of all straps. As an alternative to blocking at the ends, anchoring the strap to a stable building component with two No.8 screws shall be permitted.
A table appears here in the adopted code. Refer to the official source for the full table.
FIGURE 505.3.1 (1) FLOOR TO EXTERIOR LOAD-BEARING WALL STUD CONNECTION
A table appears here in the adopted code. Refer to the official source for the full table.
FIGURE R505.3.1 (2) FLOOR TO WOOD SILL CONNECTION
FIGURE R505.3.1 (3) FLOOR TO FOUNDATION CONNECTION
FIGURE R505.3.1 (4) CANTILEVERED FLOOR TO FOUNDATION CONNECTION
FIGURE R505.3.1 (5) CANTILEVERED FLOOR TO WOOD SILL CONNECTION
FIGURE R505.3.1 (6) CANTILEVERED FLOOR TO EXTERIOR LOAD-BEARING WALL CONNECTION
FIGURE R505.3.1 (7) CONTINUOUS SPAN JOIST SUPPORTED ON INTERIOR LOAD-BEARING WALL
FIGURE R505.3.1 (8) LAPPED JOISTS SUPPORTED ON INTERIOR LOAD-BEARING WALL
FIGURE R505.3.1 (9) BEARING STIFFENERS FOR END JOISTS
A table appears here in the adopted code. Refer to the official source for the full table.
FIGURE R505.3.3.2(1) JOIST BLOCKING (SOLID)
A table appears here in the adopted code. Refer to the official source for the full table.
FIGURE R505.3.3.2(2) JOIST BLOCKING (STRAP)
A table appears here in the adopted code. Refer to the official source for the full table.
R505.3.3.3 Blocking at interior bearing supports. Blocking is not required for continuous back-to-back floorjoists at bearing supports. Blocking shall be installed between every otherjoist for single continuous floorjoists across bearing supports in accordance with Figure R505.3.1 (7). Blocking shall consist of C-shape or track section with a minimum thickness of 33 mils (0.84 mm). Blocking shall be fastened to each adjacentjoist through a 33-mil (0.84 mm) clip angle, bent web of blocking or flanges of web stiffeners with two No. 8 screws on each side. The minimum depth of the blocking shall be equal to the depth of the joist minus 2 inches (51 mm). The minimum length of the angle shall be equal to the depth of the joist minus 2 inches (51 mm). R505.3.3.4 Blocking at cantilevers. Blocking shall be installed between every other joist over cantilever bearing supports in accordance with Figure R505.3.1 (4), R505.3.1 (5) or R505.3.1 (6). Blocking shall consist of C-shape or track section with minimum thickness of 33 mils (0.84 mm). Blocking shall be fastened to each adjacentjoist through bent web of blocking, 33 mil clip angle or flange of web stiffener with two No.8 screws at each end. The depth of the blocking shall be equal to the depth of the joist. The minimum length of the angle shall be equal to the depth of the joist minus 2 inches (51 mm). Blocking shall be fastened through the floor sheathing and to the support with three No.8 screws (top and bottom). R505.3.4 Bearing stiffeners. Bearing stiffeners shall be installed at each joist bearing location in accordance with this section, except for joists lapped over an interior support not carrying a load-bearing wall above. Floorjoists supportingjamb studs with multiple members shall have two bearing stiffeners in accordance with Figure R505.3.4(1). Bearing stiffeners shall be fabricated from a C-shaped, track or clip angle member in accordance with the one of following: C-shaped bearing stiffeners: 1.1. Where the joist is not carrying a load-bearing wall above, the bearing stiffener shall be a minimum 33 mil (0.84 mm) thickness. 1.2. Where thejoist is carrying a load-bearing wall above, the bearing stiffener shall be at least the same designation thickness as the wall stud above. Track bearing stiffeners: 2.1. Where the joist is not carrying a load-bearing wall above, the bearing stiffener shall be a minimum 43 mil (1.09 mm) thickness. 2.2. Where thejoist is carrying a load-bearing wall above, the bearing stiffener shall be at least one designation thickness greater than the wall stud above. Clip angle bearing stiffeners: Where the clip angle bearing stiffener is fastened to both the web of the member it is stiffening and an adjacent rim track using the fastener pattern shown in Figure R505.3.4(2), the bearing stiffener shall be a minimum 2-inch by 2-inch (51 mm by 51 mm) angle sized in accordance with Tables R505.3.4 (1), R505.3.4(2), R505.3.4(3), and R505.3.4(4). The minimum length of a bearing stiffener shall be the depth of member being stiffened minus 3/8 inch (9.5 mm). Each bearing stiffener shall be fastened to the web of the member it is stiffening as shown in Figure R505.3.4(2). Each clip angle bearing stiffener shall also be fastened to the web of the adjacent rim track using the fastener pattern shown in Figure R505.3.4(2). No.8 screws shall be used for C-shaped and track members of any thickness and for clip angle members with a designation thickness less than or equal to 54. No.1 0 screws shall be used for clip angle members with a designation thickness greater than 54.
R505.3.3.3 Blocking at interior bearing supports. Blocking is not required for continuous back-to-back floorjoists at bearing supports. Blocking shall be installed between every otherjoist for single continuous floorjoists across bearing supports in accordance with Figure R505.3.1 (7). Blocking shall consist of C-shape or track section with a minimum thickness of 33 mils (0.84 mm). Blocking shall be fastened to each adjacentjoist through a 33-mil (0.84 mm) clip angle, bent web of blocking or flanges of web stiffeners with two No. 8 screws on each side. The minimum depth of the blocking shall be equal to the depth of the joist minus 2 inches (51 mm). The minimum length of the angle shall be equal to the depth of the joist minus 2 inches (51 mm). R505.3.3.4 Blocking at cantilevers. Blocking shall be installed between every other joist over cantilever bearing supports in accordance with Figure R505.3.1 (4), R505.3.1 (5) or R505.3.1 (6). Blocking shall consist of C-shape or track section with minimum thickness of 33 mils (0.84 mm). Blocking shall be fastened to each adjacentjoist through bent web of blocking, 33 mil clip angle or flange of web stiffener with two No.8 screws at each end. The depth of the blocking shall be equal to the depth of the joist. The minimum length of the angle shall be equal to the depth of the joist minus 2 inches (51 mm). Blocking shall be fastened through the floor sheathing and to the support with three No.8 screws (top and bottom).
R505.3.3.3 Blocking at interior bearing supports. Blocking is not required for continuous back-to-back floorjoists at bearing supports. Blocking shall be installed between every otherjoist for single continuous floorjoists across bearing supports in accordance with Figure R505.3.1 (7). Blocking shall consist of C-shape or track section with a minimum thickness of 33 mils (0.84 mm). Blocking shall be fastened to each adjacentjoist through a 33-mil (0.84 mm) clip angle, bent web of blocking or flanges of web stiffeners with two No. 8 screws on each side. The minimum depth of the blocking shall be equal to the depth of the joist minus 2 inches (51 mm). The minimum length of the angle shall be equal to the depth of the joist minus 2 inches (51 mm).
R505.3.3.4 Blocking at cantilevers. Blocking shall be installed between every other joist over cantilever bearing supports in accordance with Figure R505.3.1 (4), R505.3.1 (5) or R505.3.1 (6). Blocking shall consist of C-shape or track section with minimum thickness of 33 mils (0.84 mm). Blocking shall be fastened to each adjacentjoist through bent web of blocking, 33 mil clip angle or flange of web stiffener with two No.8 screws at each end. The depth of the blocking shall be equal to the depth of the joist. The minimum length of the angle shall be equal to the depth of the joist minus 2 inches (51 mm). Blocking shall be fastened through the floor sheathing and to the support with three No.8 screws (top and bottom).
R505.3.4 Bearing stiffeners. Bearing stiffeners shall be installed at each joist bearing location in accordance with this section, except for joists lapped over an interior support not carrying a load-bearing wall above. Floorjoists supportingjamb studs with multiple members shall have two bearing stiffeners in accordance with Figure R505.3.4(1). Bearing stiffeners shall be fabricated from a C-shaped, track or clip angle member in accordance with the one of following:
- C-shaped bearing stiffeners: 1.1. Where the joist is not carrying a load-bearing wall above, the bearing stiffener shall be a minimum 33 mil (0.84 mm) thickness. 1.2. Where thejoist is carrying a load-bearing wall above, the bearing stiffener shall be at least the same designation thickness as the wall stud above.
- Track bearing stiffeners: 2.1. Where the joist is not carrying a load-bearing wall above, the bearing stiffener shall be a minimum 43 mil (1.09 mm) thickness. 2.2. Where thejoist is carrying a load-bearing wall above, the bearing stiffener shall be at least one designation thickness greater than the wall stud above.
- Clip angle bearing stiffeners: Where the clip angle bearing stiffener is fastened to both the web of the member it is stiffening and an adjacent rim track using the fastener pattern shown in Figure R505.3.4(2), the bearing stiffener shall be a minimum 2-inch by 2-inch (51 mm by 51 mm) angle sized in accordance with Tables R505.3.4 (1), R505.3.4(2), R505.3.4(3), and R505.3.4(4).
1.1. Where the joist is not carrying a load-bearing wall above, the bearing stiffener shall be a minimum 33 mil (0.84 mm) thickness. 1.2. Where thejoist is carrying a load-bearing wall above, the bearing stiffener shall be at least the same designation thickness as the wall stud above.
1.1. Where the joist is not carrying a load-bearing wall above, the bearing stiffener shall be a minimum 33 mil (0.84 mm) thickness.
1.2. Where thejoist is carrying a load-bearing wall above, the bearing stiffener shall be at least the same designation thickness as the wall stud above.
2.1. Where the joist is not carrying a load-bearing wall above, the bearing stiffener shall be a minimum 43 mil (1.09 mm) thickness. 2.2. Where thejoist is carrying a load-bearing wall above, the bearing stiffener shall be at least one designation thickness greater than the wall stud above.
2.1. Where the joist is not carrying a load-bearing wall above, the bearing stiffener shall be a minimum 43 mil (1.09 mm) thickness.
2.2. Where thejoist is carrying a load-bearing wall above, the bearing stiffener shall be at least one designation thickness greater than the wall stud above.
The minimum length of a bearing stiffener shall be the depth of member being stiffened minus 3/8 inch (9.5 mm). Each bearing stiffener shall be fastened to the web of the member it is stiffening as shown in Figure R505.3.4(2). Each clip angle bearing stiffener shall also be fastened to the web of the adjacent rim track using the fastener pattern shown in Figure R505.3.4(2). No.8 screws shall be used for C-shaped and track members of any thickness and for clip angle members with a designation thickness less than or equal to 54. No.1 0 screws shall be used for clip angle members with a designation thickness greater than 54.
FIGURE R505.3.4(1) BEARING STIFFENERS UNDER JAMB STUDS
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
FIGURE R505.3.4(2) BEARING STIFFENER
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
R505.3.5 Cutting and notching. Flanges and lips of load-bearing cold-formed steel floor framing members shall not be cut or notched. R505.3.6 Floor cantilevers. Floor cantilevers for the top floor of a two- or three-story building or the first floor of a one-story building shall not exceed 24 inches (610 mm). Cantilevers, not exceeding 24 inches (610 mm) and supporting two stories and roof (Le., first floor of a two-story building), shall also be permitted provided that all cantilevered joists are doubled (nested or back-to-back). The doubled cantilevered joists shall extend a minimum of 6 feet (1829 mm) toward the inside and shall be fastened with a minimum of two No.8 screws spaced at 24 inches (610 mm) on center through the webs (for back-to-back) or flanges (for nested joists). R505.3.7 Splicing. Joists and other structural members shall not be spliced. Splicing of tracks shall conform to Figure R505.3.7. R505.3.8 Framing of floor openings. Openings in floors shall be framed with header and trimmerjoists. Headerjoist spans shall not exceed 6 feet (1829 mm) or 8 feet (2438 mm) in length in accordance with Figure R505.3.8(1) or R505.3.8(2), respectively. Header and trimmer joists shall be fabricated fromjoist and track members, having a minimum size and thickness at least equivalent to the adjacent floor joists and shall be installed in accordance with Figures R505.3.8(1), R505.3.8(2), R505.3.8(3), and R505.3.8(4). Each header joist shall be connected to trimmer joists with four 2-inch-by-2-inch (51mm by 51 mm) clip angles. Each clip angle shall be fastened to both the header and trimmer joists with four No.8 screws, evenly spaced, through each leg of the clip angle. The clip angles shall have a thickness not less than that of the floor joist. Each track section for a built-up header or trimmer joist shall extend the full length of the joist (continuous).
R505.3.5 Cutting and notching. Flanges and lips of load-bearing cold-formed steel floor framing members shall not be cut or notched.
R505.3.6 Floor cantilevers. Floor cantilevers for the top floor of a two- or three-story building or the first floor of a one-story building shall not exceed 24 inches (610 mm). Cantilevers, not exceeding 24 inches (610 mm) and supporting two stories and roof (Le., first floor of a two-story building), shall also be permitted provided that all cantilevered joists are doubled (nested or back-to-back). The doubled cantilevered joists shall extend a minimum of 6 feet (1829 mm) toward the inside and shall be fastened with a minimum of two No.8 screws spaced at 24 inches (610 mm) on center through the webs (for back-to-back) or flanges (for nested joists).
R505.3.7 Splicing. Joists and other structural members shall not be spliced. Splicing of tracks shall conform to Figure R505.3.7.
R505.3.8 Framing of floor openings. Openings in floors shall be framed with header and trimmerjoists. Headerjoist spans shall not exceed 6 feet (1829 mm) or 8 feet (2438 mm) in length in accordance with Figure R505.3.8(1) or R505.3.8(2), respectively. Header and trimmer joists shall be fabricated fromjoist and track members, having a minimum size and thickness at least equivalent to the adjacent floor joists and shall be installed in accordance with Figures R505.3.8(1), R505.3.8(2), R505.3.8(3), and R505.3.8(4). Each header joist shall be connected to trimmer joists with four 2-inch-by-2-inch (51mm by 51 mm) clip angles. Each clip angle shall be fastened to both the header and trimmer joists with four No.8 screws, evenly spaced, through each leg of the clip angle. The clip angles shall have a thickness not less than that of the floor joist. Each track section for a built-up header or trimmer joist shall extend the full length of the joist (continuous).
FIGURE R505.3.7 TRACK SPLICE
FIGURE R505.3.8(1) COLD-FORMED STEEL FLOOR CONSTRUCTION: 6-FOOT FLOOR OPENING
FIGURE R505.3.8(2) COLD-FORMED STEEL FLOOR CONSTRUCTION: 8-FOOT FLOOR OPENING
FIGURE R505.3.8(3) COLD-FORMED STEEL FLOOR CONSTRUCTION: FLOOR HEADER TO TRIMMER CONNECTION-6-FOOT OPENING
FIGURE R505.3.8(4) COLD-FORMED STEEL FLOOR CONSTRUCTION: FLOOR HEADER TO TRIMMER CONNECTION-8-FOOT OPENING

R506 — Concrete Floors (on Ground)
R506.1 General. Concrete slab-on-ground floors shall be a minimum 3.5 inches (89 mm) thick (for expansive soils, see Section R403.1.8). The specified compressive strength of concrete shall be as set forth in Section R402.2.
R506.2 Site preparation. The area within the foundation walls shall have all vegetation, top soil and foreign material removed.
R506.2.1 Fill. Fill material shall be free of vegetation and foreign material. The fill shall be compacted to assure uniform support ofthe slab, and except where approved, the fill depths shall not exceed 24 inches (610 mm) for clean sand or gravel and 8 inches (203 mm) for earth. R506.2.2 Base. A 4-inch-thick (102 mm) base course consisting of clean graded sand, gravel, crushed stone or crushed blast-furnace slag passing a 2-inch (51 mm) sieve shall be placed on the prepared subgrade when the slab is below grade. Exception: A base course is not required when the concrete slab is installed on well-drained or sand-gravel mixture soils classified as Group I according to the United Soil Classification System in accordance with Table R405.1. R506.2.3 Vapor retarder. A 6 mil (0.006 inch; 152 μm) polyethylene or approvedvapor retarder with joints lapped not less than 6 inches (152 mm) shall be placed between the concrete floor slab and the base course or the prepared subgrade where no base course exists. Exception: The vapor retarder may be omitted: From detached garages, utility buildings and other unheated accessory structures. For unheated storage rooms having an area of less than 70 square feet (6.5 m2) and carports. From driveways, walks, patios and other flatwork not likely to be enclosed and heated at a later date. Where approved by the building official, based on local site conditions. R506.2.4 Reinforcement support. Where provided in slabs on ground, reinforcement shall be supported to remain in place from the center to upper one third of the slab for the duration of the concrete placement.
R506.2.1 Fill. Fill material shall be free of vegetation and foreign material. The fill shall be compacted to assure uniform support ofthe slab, and except where approved, the fill depths shall not exceed 24 inches (610 mm) for clean sand or gravel and 8 inches (203 mm) for earth.
R506.2.2 Base. A 4-inch-thick (102 mm) base course consisting of clean graded sand, gravel, crushed stone or crushed blast-furnace slag passing a 2-inch (51 mm) sieve shall be placed on the prepared subgrade when the slab is below grade.
Exception: A base course is not required when the concrete slab is installed on well-drained or sand-gravel mixture soils classified as Group I according to the United Soil Classification System in accordance with Table R405.1.
Exception: A base course is not required when the concrete slab is installed on well-drained or sand-gravel mixture soils classified as Group I according to the United Soil Classification System in accordance with Table R405.1.
R506.2.3 Vapor retarder. A 6 mil (0.006 inch; 152 μm) polyethylene or approvedvapor retarder with joints lapped not less than 6 inches (152 mm) shall be placed between the concrete floor slab and the base course or the prepared subgrade where no base course exists.
Exception: The vapor retarder may be omitted: From detached garages, utility buildings and other unheated accessory structures. For unheated storage rooms having an area of less than 70 square feet (6.5 m2) and carports. From driveways, walks, patios and other flatwork not likely to be enclosed and heated at a later date. Where approved by the building official, based on local site conditions.
Exception: The vapor retarder may be omitted:
- From detached garages, utility buildings and other unheated accessory structures.
- For unheated storage rooms having an area of less than 70 square feet (6.5 m2) and carports.
- From driveways, walks, patios and other flatwork not likely to be enclosed and heated at a later date.
- Where approved by the building official, based on local site conditions.
R506.2.4 Reinforcement support. Where provided in slabs on ground, reinforcement shall be supported to remain in place from the center to upper one third of the slab for the duration of the concrete placement.
Worked example
Scenario: A designer is specifying the concrete slab for a garage floor that will be placed directly on the ground.
Explanation: The concrete slab must be at least 3.5 inches (89 mm) thick. The specified compressive strength of the concrete must also conform to the requirements outlined in Section R402.2. If the site has expansive soils, Section R403.1.8 must be referenced for additional requirements.
Frequently asked questions
What types of floors are covered by Chapter 5?
Chapter 5 covers the design and construction of all floors, including those made of wood, pressure-treated wood on ground, cold-formed steel, and concrete slabs-on-ground, as well as attic floors housing equipment.
Are there specific identification requirements for wood framing members?
Yes, load-bearing dimension lumber for joists, beams, and girders must be identified by a grade mark from an approved grading agency or by a certificate of inspection.
What is the minimum thickness for a concrete slab-on-ground floor?
Concrete slab-on-ground floors must be a minimum of 3.5 inches (89 mm) thick, with additional considerations for expansive soils.