This chapter establishes requirements for the safe storage and use of organic peroxides, referencing Chapter 27 for general hazardous materials provisions.
3901 — General
3901.1 Scope. The storage and use of organic peroxides shall be in accordance with this chapter and Chapter 27.
Unclassified detonable organic peroxides that are capable of detonation in their normal shipping containers under conditions of fire exposure shall be stored in accordance with Chapter 33.
3901.2 Permits. Permits shall be required for organic peroxides as set forth in Section 105.6.
3902 — Definitions
3902.1 Definition. The following word and term shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.
ORGANIC PEROXIDE. An organic compound that contains the bivalent -0-0- structure and which may be considered to be a structural derivative of hydrogen peroxide where one or both of the hydrogen atoms have been replaced by an organic radical. Organic peroxides can present an explosion hazard (detonation or defJagration) or they can be shock sensitive. They can also decompose into various unstable compounds over an extended period of time.
Class I. Describes those formulations that are capable of defJagration but not detonation. Class II. Describes those formulations that burn very rapidly and that pose a moderate reactivity hazard. Class III. Describes those formulations that burn rapidly and that pose a moderate reactivity hazard. Class IV. Describes those formulations that burn in the same manner as ordinary combustibles and that pose a minimal reactivity hazard. Class V. Describes those formulations that burn with less intensity than ordinary combustibles or do not sustain combustion and that pose no reactivity hazard. Unclassified detonable. Organic peroxides that are capable of detonation. These peroxides pose an extremely high-explosion hazard through rapid explosive decomposition.
Class I. Describes those formulations that are capable of defJagration but not detonation.
Class II. Describes those formulations that burn very rapidly and that pose a moderate reactivity hazard.
Class III. Describes those formulations that burn rapidly and that pose a moderate reactivity hazard.
Class IV. Describes those formulations that burn in the same manner as ordinary combustibles and that pose a minimal reactivity hazard.
Class V. Describes those formulations that burn with less intensity than ordinary combustibles or do not sustain combustion and that pose no reactivity hazard.
Unclassified detonable. Organic peroxides that are capable of detonation. These peroxides pose an extremely high-explosion hazard through rapid explosive decomposition.
3903 — General Requirements
3903.1 Quantities not exceeding the maximum allowable quantity per control area. The storage and use of organic peroxides in amounts not exceeding the maximum allowable quantity per control area indicated in Section 2703.1 shall be in accordance with Sections 2701, 2703, 3901 and 3903.
3903.1.1 Special limitations for indoor storage and use by occupancy. The indoor storage and use of organic peroxides shall be in accordance with Sections 3903.1.1.1 through 3903.1.1.4.
3903.1.1.1 Group A, E, I or U occupancies. In Group A, E, I or U occupancies, any amount of unclassified detonable and Class I organic peroxides shall be stored in accordance with the following: Unclassified detonable and Class I organic peroxides shall be stored in hazardous materials storage cabinets complying with Section 2703.8.7. The hazardous materials storage cabinets shall not contain other storage. 3903.1.1.2 Group R occupancies. Unclassified detonable and Class I organic peroxides shall not be stored or used within Group R occupancies. 3903.1.1.3 Group B, F, M or S occupancies. Unclassified detonable and Class I organic peroxides shall not be stored or used in offices, or retail sales areas of Group B, F, M or S occupancies. 3903.1.1.4 Classrooms. In classrooms in Group B, F or M occupancies, any amount of unclassified detonable and Class 1 organic peroxides shall be stored in accordance with the following. Unclassified detonable and Class 1 organic peroxides shall be stored in hazardous materials storage cabinets complying with Section 2703.8.7. The hazardous materials storage cabinets shall not contain other storage. 3903.2 Quantities exceeding the maximum allowable quantity per control area. The storage and use of organic peroxides in amounts exceeding the maximum allowable quantity per control area indicated in Section 2703.1 shall be in accordance with Chapter 27 and this chapter.
3903.1.1.1 Group A, E, I or U occupancies. In Group A, E, I or U occupancies, any amount of unclassified detonable and Class I organic peroxides shall be stored in accordance with the following:
Unclassified detonable and Class I organic peroxides shall be stored in hazardous materials storage cabinets complying with Section 2703.8.7. The hazardous materials storage cabinets shall not contain other storage.
- Unclassified detonable and Class I organic peroxides shall be stored in hazardous materials storage cabinets complying with Section 2703.8.7.
- The hazardous materials storage cabinets shall not contain other storage.
3903.1.1.2 Group R occupancies. Unclassified detonable and Class I organic peroxides shall not be stored or used within Group R occupancies.
3903.1.1.3 Group B, F, M or S occupancies. Unclassified detonable and Class I organic peroxides shall not be stored or used in offices, or retail sales areas of Group B, F, M or S occupancies.
3903.1.1.4 Classrooms. In classrooms in Group B, F or M occupancies, any amount of unclassified detonable and Class 1 organic peroxides shall be stored in accordance with the following.
Unclassified detonable and Class 1 organic peroxides shall be stored in hazardous materials storage cabinets complying with Section 2703.8.7. The hazardous materials storage cabinets shall not contain other storage.
- Unclassified detonable and Class 1 organic peroxides shall be stored in hazardous materials storage cabinets complying with Section 2703.8.7.
- The hazardous materials storage cabinets shall not contain other storage.
3903.2 Quantities exceeding the maximum allowable quantity per control area. The storage and use of organic peroxides in amounts exceeding the maximum allowable quantity per control area indicated in Section 2703.1 shall be in accordance with Chapter 27 and this chapter.
Worked example
Scenario: A university chemistry lab keeps a small stock of organic peroxides, which falls below the maximum allowable quantity per control area.
Explanation: To comply, the lab must adhere to Sections 2701 (general requirements for hazardous materials), 2703 (control areas), 3901 (scope), and 3903 (general requirements for quantities not exceeding limits).
3904 — Storage
3904.1 Indoor storage. Indoor storage of organic peroxides in amounts exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1 (1) shall be in accordance with Sections 2701, 2703, 2704 and this chapter.
Indoor storage of unclassified detonable organic peroxides that are capable of detonation in their normal shipping containers under conditions of fire exposure shall be stored in accordance with Chapter 33.
3904.1.1 Detached storage. Storage of organic peroxides shall be in detached buildings when required by Section 2703.8.2.
3904.1.1 Detached storage. Storage of organic peroxides shall be in detached buildings when required by Section 2703.8.2.
3904.1.2 Distance from detached storage buildings to exposures. In addition to the requirements of the International BUilding Code, detached storage buildings shall be located in accordance with Table 3904.1.2. 3904.1.3 Liquid-tight floor. In addition to the requirements of Section 2704.12, floors of storage areas shall be of liquid-tight construction. 3904.1.4 Electrical wiring and equipment. In addition to the requirements of Section 2703.9.4, electrical wiring and equipment in storage areas for Class I or II organic peroxides shall comply with the requirements for electrical Class I, Division 2 locations. 3904.1.5 Smoke detection. An approvedsupervised smoke detection system in accordance with Section 907 shall be provided in rooms or areas where Class I, II or III organic peroxides are stored. Activation of the smoke detection system shall sound a local alarm. Exception: A smoke detection system shall not be required in detached storage buildings equipped throughout with an approved automatic fire-extinguishing system complying with Chapter 9. 3904.1.6 Maximum quantities. Maximum allowable quantities per building in a mixed occupancy building shall not exceed the amounts set forth in Table 2703.8.2. Maximum allowable quantities per building in a detached storage building shall not exceed the amounts specified in Table 3904.1.2. 3904.1.7 Storage arrangement. Storage arrangements for organic peroxides shall be in accordance with Table 3904.1.7 and shall comply with all of the following: Containers and packages in storage areas shall be closed. Bulk storage shall not be in piles or bins. A minimum 2-foot (610 mm) clear space shall be maintained between storage and uninsulated metal walls. Fifty-five-gallon (208 L) drums shall not be stored more than one drum high. 3904.1.8 Location in building. The storage of Class I or II organic peroxides shall be on the ground floor. Class III organic peroxides shall not be stored in basements. 3904.1.9 Contamination. Organic peroxides shall be stored in their original DOTn shipping containers. Organic peroxides shall be stored in a manner to prevent contamination. 3904.1.10 Explosion control. Indoor storage rooms, areas and buildings containing unclassified detonable and Class I organic peroxides shall be provided with explosion control in accordance with Section 911. 3904.1.11 Standby power. Standby power in accordance with Section 604 shall be provided for storage areas of Class I and unclassified detonable organic peroxide.
3904.1.2 Distance from detached storage buildings to exposures. In addition to the requirements of the International BUilding Code, detached storage buildings shall be located in accordance with Table 3904.1.2.
3904.1.3 Liquid-tight floor. In addition to the requirements of Section 2704.12, floors of storage areas shall be of liquid-tight construction.
3904.1.4 Electrical wiring and equipment. In addition to the requirements of Section 2703.9.4, electrical wiring and equipment in storage areas for Class I or II organic peroxides shall comply with the requirements for electrical Class I, Division 2 locations.
3904.1.5 Smoke detection. An approvedsupervised smoke detection system in accordance with Section 907 shall be provided in rooms or areas where Class I, II or III organic peroxides are stored. Activation of the smoke detection system shall sound a local alarm.
Exception: A smoke detection system shall not be required in detached storage buildings equipped throughout with an approved automatic fire-extinguishing system complying with Chapter 9.
Exception: A smoke detection system shall not be required in detached storage buildings equipped throughout with an approved automatic fire-extinguishing system complying with Chapter 9.
3904.1.6 Maximum quantities. Maximum allowable quantities per building in a mixed occupancy building shall not exceed the amounts set forth in Table 2703.8.2. Maximum allowable quantities per building in a detached storage building shall not exceed the amounts specified in Table 3904.1.2.
3904.1.7 Storage arrangement. Storage arrangements for organic peroxides shall be in accordance with Table 3904.1.7 and shall comply with all of the following:
Containers and packages in storage areas shall be closed. Bulk storage shall not be in piles or bins. A minimum 2-foot (610 mm) clear space shall be maintained between storage and uninsulated metal walls. Fifty-five-gallon (208 L) drums shall not be stored more than one drum high.
- Containers and packages in storage areas shall be closed.
- Bulk storage shall not be in piles or bins.
- A minimum 2-foot (610 mm) clear space shall be maintained between storage and uninsulated metal walls.
- Fifty-five-gallon (208 L) drums shall not be stored more than one drum high.
3904.1.8 Location in building. The storage of Class I or II organic peroxides shall be on the ground floor. Class III organic peroxides shall not be stored in basements.
3904.1.9 Contamination. Organic peroxides shall be stored in their original DOTn shipping containers. Organic peroxides shall be stored in a manner to prevent contamination.
3904.1.10 Explosion control. Indoor storage rooms, areas and buildings containing unclassified detonable and Class I organic peroxides shall be provided with explosion control in accordance with Section 911.
3904.1.11 Standby power. Standby power in accordance with Section 604 shall be provided for storage areas of Class I and unclassified detonable organic peroxide.
3904.2 Outdoor storage. Outdoor storage of organic peroxides in amounts exceeding the maximum allowable quantities per control area indicated in Table 2703.1.1 (3) shall be in accordance with Sections 2701, 2703, 2704 and this chapter.
3904.2.1 Distance from storage to exposures. Outdoor storage areas for organic peroxides shall be located in accordance with Table 3904.1.2. 3904.2.2 Electrical wiring and equipment. In addition to the requirements of Section 2703.9.4, electrical wiring and equipment in outdoor storage areas containing unclassified detonable, Class I or II organic peroxides shall comply with the requirements for electrical Class I, Division 2 locations. 3904.2.3 Maximum quantities. Maximum quantities of organic peroxides in outdoor storage shall be in accordance with Table 3904.1.2. 3904.2.4 Storage arrangement. Storage arrangements shall be in accordance with Table 3904.1.7. 3904.2.5 Separation. In addition to the requirements of Section 2703.9.8, outdoor storage areas for organic peroxides in amounts exceeding those specified in Table 2703.8.2 shall be located a minimum distance of 50 feet (15 240 mm) from other hazardous material storage.
3904.2.1 Distance from storage to exposures. Outdoor storage areas for organic peroxides shall be located in accordance with Table 3904.1.2.
3904.2.2 Electrical wiring and equipment. In addition to the requirements of Section 2703.9.4, electrical wiring and equipment in outdoor storage areas containing unclassified detonable, Class I or II organic peroxides shall comply with the requirements for electrical Class I, Division 2 locations.
3904.2.3 Maximum quantities. Maximum quantities of organic peroxides in outdoor storage shall be in accordance with Table 3904.1.2.
3904.2.4 Storage arrangement. Storage arrangements shall be in accordance with Table 3904.1.7.
3904.2.5 Separation. In addition to the requirements of Section 2703.9.8, outdoor storage areas for organic peroxides in amounts exceeding those specified in Table 2703.8.2 shall be located a minimum distance of 50 feet (15 240 mm) from other hazardous material storage.
A table appears here in the adopted code. Refer to the official source for the full table.
A table appears here in the adopted code. Refer to the official source for the full table.
Worked example
Scenario: A chemical manufacturer plans to build a dedicated warehouse for organic peroxides, and the total quantity will exceed the maximum allowable limit.
Explanation: Because the quantities exceed the maximum allowable limits per Table 2703.1.1 (1), the indoor storage facility must comply with Sections 2701, 2703, 2704 (storage requirements for hazardous materials), and Chapter 39.
3905 — Use
3905.1 General. The use of organic peroxides in amounts exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1 (1) or 2703.1.1 (3) shall be in accordance with Sections 2701, 2703, 2705 and this chapter.
Worked example
Scenario: A pharmaceutical company uses a large volume of organic peroxides in its manufacturing process, exceeding the maximum allowable quantity per control area.
Explanation: The use of these organic peroxides must comply with Sections 2701, 2703, 2705 (use requirements for hazardous materials), and Chapter 39, as the quantity surpasses the limits in Table 2703.1.1 (1) or (3).
Frequently asked questions
What code sections apply to organic peroxides?
The storage and use of organic peroxides are governed by this chapter (Chapter 39) and Chapter 27 of the code.
Where can I find the maximum allowable quantities for organic peroxides?
Maximum allowable quantities for organic peroxides are indicated in Section 2703.1 and Table 2703.1.1 (1) or (3).
Are there different requirements for small versus large quantities of organic peroxides?
Yes, quantities not exceeding the maximum allowable quantity follow Section 3903, while quantities exceeding this limit have additional requirements detailed in Sections 3904 (storage) and 3905 (use), referencing specific sections of Chapter 27.