Minimum Plumbing Fixture Requirements by Occupancy (IPC Table 403.1)
IPC Section 403 sets the minimum number of water closets, lavatories, bathtubs or showers, drinking fountains and service sinks by applying the Table 403.1 ratio for the building's use to half the occupant load for each sex and rounding up.
On this page
Last updated October 27, 2026 · Fixture ratios, calculation rules and exceptions are taken from the [2021 International Plumbing Code, Chapter 4, Fixtures, Faucets and Fixture Fittings](https://codes.iccsafe.org/content/IPC2021P2/chapter-4-fixtures-faucets-and-fixture-fittings) (Table 403.1 and Sections 403, 405, 410, 419 and 424). Dwelling requirements come from [2021 International Residential Code Chapter 3](https://codes.iccsafe.org/content/IRC2021P2/chapter-3-building-planning) (Section R306) and [Chapter 27, Plumbing Fixtures](https://codes.iccsafe.org/content/IRC2021P2/chapter-27-plumbing-fixtures) (Section P2705). The restaurant occupant load uses the IBC 2021 Table 1004.5 factor for unconcentrated assembly. Section numbering follows the 2021 editions; these are typical model-code values, so verify every ratio and exception against the edition adopted by the authority having jurisdiction, any state plumbing code (some states adopt the Uniform Plumbing Code instead) and local amendments.
Direct answer
Under the 2021 International Plumbing Code, Section 403.1 requires plumbing fixtures in the minimum number shown in Table 403.1, based on the actual use of the space and the occupant load determined by the International Building Code. Section 403.1.1 divides that occupant load in half for each sex, applies each fixture ratio and rounds every fraction up; where one set of toilet rooms serves several occupancies, the fractions are summed before rounding. Typical ratios are 1 water closet per 25 occupants for the first 50 and 1 per 50 after that in a Group B office, 1 per 75 in a restaurant, 1 per 40 in a bar, 1 per 50 in a school and 1 per 500 in a retail store. Section 403.2 requires separate facilities for each sex, except in dwelling and sleeping units, spaces with 15 or fewer occupants, mercantile uses of 100 or fewer, business uses of 25 or fewer, single-user rooms and all-gender rooms with enclosed water closet compartments.
Content and cited inputs reviewed by Harth team · Published 2026-10-27 · Updated 2026-10-27.
What are the key takeaways?
- Occupant split: Half the occupant load per sex, fractions rounded up
- Office (Group B) water closets: 1 per 25 for the first 50, then 1 per 50
- Restaurant water closets: 1 per 75 for each sex
- Single shared facility: Total occupant load of 15 or fewer
How is the minimum number of plumbing fixtures calculated?
The International Plumbing Code (IPC) sets plumbing fixture counts in Section 403. The method in the 2021 edition has five steps, and each one changes the answer if it is skipped.
- Find the occupant load. IPC Section 403.1 takes the number of occupants from the International Building Code, so the count starts with the Chapter 10 occupant load calculation, not a separate plumbing number.
- Pick the row by actual use. Table 403.1 is applied "based on the actual use of the building or space". A use the table does not list is considered individually by the code official.
- Split by sex. Section 403.1.1 divides the total occupant load in half. A different split is allowed only where approved statistical data support it, and facilities designed for all genders are counted on 100 percent of the load.
- Apply each ratio and round up. A ratio such as "1 per 75" means one fixture for every 75 persons or any fraction of 75 (footnote a). Every fractional result rounds up to the next whole fixture.
- Sum fractions across occupancies. Where one set of toilet rooms serves more than one occupancy, the fractions for each occupancy are added first and rounded once at the end.
Water closets and lavatories have separate male and female columns in Table 403.1. The drinking fountain, bathtub or shower and service sink columns are not split by sex and are normally counted on the total occupant load; confirm that reading with the code official where a fraction decides the count.
Worked example: a 160-seat restaurant
A 2,400-square-foot dining room with tables and chairs has an occupant load of 160 at the IBC Table 1004.5 factor of 15 square feet net per occupant. Splitting it gives 80 men and 80 women.
| Fixture | Table 403.1 ratio (restaurants) | Calculation | Required |
|---|---|---|---|
| Water closets, male | 1 per 75 | 80 / 75 = 1.07 | 2 |
| Water closets, female | 1 per 75 | 80 / 75 = 1.07 | 2 |
| Lavatories, male | 1 per 200 | 80 / 200 = 0.40 | 1 |
| Lavatories, female | 1 per 200 | 80 / 200 = 0.40 | 1 |
| Drinking fountain | 1 per 500 | 160 / 500 = 0.32 | 1, or none if free water is served in a container (Section 410.4) |
| Service sink | 1 | Fixed | 1 |
In the men's room, Section 424.2 lets urinals replace not more than 67 percent of the required water closets in an assembly occupancy. Sixty-seven percent of 2 is 1.34, so one urinal may replace one water closet, leaving one water closet and one urinal. Footnote d adds any seasonal outdoor seating to the occupant load before the calculation.
Worked example: shared toilet rooms for two occupancies
A small building has a 60-occupant Group B office and a 120-occupant Group M shop sharing one pair of toilet rooms. Per sex that is 30 office occupants and 60 retail occupants.
| Fixture per sex | Office fraction | Retail fraction | Sum | Required per sex |
|---|---|---|---|---|
| Water closets | 30 / 25 = 1.20 | 60 / 500 = 0.12 | 1.32 | 2 |
| Lavatories | 30 / 40 = 0.75 | 60 / 750 = 0.08 | 0.83 | 1 |
Rounding each occupancy separately would have produced three water closets and two lavatories per sex. Summing first, as Section 403.1.1 requires, gives two and one. Drinking fountains on the total load are 60 / 100 + 120 / 1,000 = 0.72, so one is required, and one service sink serves the building.
When are separate men's and women's facilities not required?
Section 403.2 requires separate facilities for each sex wherever fixtures are required, with six exceptions in the 2021 IPC:
- dwelling units and sleeping units;
- structures or tenant spaces with a total occupant load, employees and customers combined, of 15 or fewer;
- mercantile occupancies with a maximum occupant load of 100 or fewer;
- business occupancies with a maximum occupant load of 25 or fewer;
- single-user toilet rooms provided under Section 403.1.2, which must be identified as available to all persons regardless of sex;
- multiple-user rooms designed for all sexes, where each water closet is in a compartment with walls or partitions and a door (Section 405.3.4) and urinals are in stalls or a visually separated area.
Section 403.2.1 also allows two family or assisted-use toilet rooms to serve as the required separate facilities where each sex would otherwise need only one water closet.
Where must the toilet rooms be, and who must be able to use them?
Section 403.3 requires toilet facilities for employees and, in buildings intended for public use, for customers, patrons and visitors. Parking garages without attendants, and quick-transaction tenants such as takeout counters with a public area of 300 square feet or less, are exempt from the public facility requirement. The route to public toilets cannot pass through kitchens, storage rooms or closets (403.3.1), and a toilet room cannot open directly into a room where food is prepared for the public (403.3.2). Outside malls, required facilities must be within one story above or below and a 500-foot path of travel (403.3.3). A toilet room for multiple occupants cannot have an egress door lockable from inside (403.3.6), and pay toilets count only in excess of the minimum (403.3.5).
What does the IRC require in a dwelling?
One- and two-family dwellings built under the International Residential Code follow IRC Section R306 rather than Table 403.1. Every dwelling unit needs a water closet, a lavatory and a bathtub or shower (R306.1), and every kitchen area needs a sink (R306.2). Kitchen sinks, lavatories, bathtubs, showers, bidets, laundry tubs and washing machine outlets need hot and cold water (R306.4). IRC Section P2705.1 sets the same layout clearances the IPC uses in Section 405.3.1: 15 inches from a water closet, lavatory or bidet centerline to a side wall or partition, 30 inches center to center between adjacent fixtures, and 21 inches of clear space in front.
IPC 2021 Table 403.1 minimum fixture ratios by occupancy
Ratios are reproduced from Table 403.1 of the 2021 International Plumbing Code. "1 per 75" means one fixture for each 75 occupants or fraction of 75. Where one value is shown for water closets or lavatories it applies to each sex. The IBC group column is an editorial cross-reference, not part of the table. Typical model-code values; verify against the AHJ-adopted edition and local amendments.
| Use (Table 403.1 description) | Typical IBC group | Water closets (male / female) | Lavatories (male / female) | Bathtubs or showers | Drinking fountains | Other |
|---|---|---|---|---|---|---|
| Theaters and buildings for the performing arts and motion pictures | A-1 | 1 per 125 / 1 per 65 | 1 per 200 | None | 1 per 500 | 1 service sink |
| Nightclubs, bars, taverns and dance halls | A-2 | 1 per 40 / 1 per 40 | 1 per 75 | None | 1 per 500 | 1 service sink |
| Restaurants, banquet halls and food courts | A-2 | 1 per 75 / 1 per 75 | 1 per 200 | None | 1 per 500 | 1 service sink |
| Casino gaming areas | A-2 | 1 per 100 for the first 400, then 1 per 250 / 1 per 50 for the first 400, then 1 per 150 | 1 per 250 for the first 750, then 1 per 500 | None | 1 per 1,000 | 1 service sink |
| Auditoriums without permanent seating, art galleries, exhibition halls, museums, lecture halls, libraries, arcades and gymnasiums | A-3 | 1 per 125 / 1 per 65 | 1 per 200 | None | 1 per 500 | 1 service sink |
| Passenger terminals and transportation facilities | A-3 | 1 per 500 / 1 per 500 | 1 per 750 | None | 1 per 1,000 | 1 service sink |
| Places of worship and other religious services | A-3 | 1 per 150 / 1 per 75 | 1 per 200 | None | 1 per 1,000 | 1 service sink |
| Coliseums, arenas, skating rinks, pools and tennis courts for indoor sporting events | A-4 | 1 per 75 for the first 1,500, then 1 per 120 / 1 per 40 for the first 1,520, then 1 per 60 | 1 per 200 / 1 per 150 | None | 1 per 1,000 | 1 service sink |
| Stadiums, amusement parks, bleachers and grandstands for outdoor sporting events | A-5 | 1 per 75 for the first 1,500, then 1 per 120 / 1 per 40 for the first 1,520, then 1 per 60 | 1 per 200 / 1 per 150 | None | 1 per 1,000 | 1 service sink |
| Offices, banks, professional services, ambulatory care, light industrial | B | 1 per 25 for the first 50, then 1 per 50 | 1 per 40 for the first 80, then 1 per 80 | None | 1 per 100 | 1 service sink (not required at 15 or fewer occupants) |
| Educational facilities | E | 1 per 50 | 1 per 50 | None | 1 per 100 | 1 service sink |
| Factory and industrial | F-1, F-2 | 1 per 100 | 1 per 100 | None | 1 per 400 | 1 service sink |
| Custodial care facilities | I-1 | 1 per 10 | 1 per 10 | 1 per 8 | 1 per 100 | 1 service sink |
| Medical care recipients in hospitals and nursing homes | I-2 | 1 per room | 1 per room | 1 per 15 | 1 per 100 | 1 service sink per floor |
| Employees in hospitals and nursing homes | I-2 | 1 per 25 | 1 per 35 | None | 1 per 100 | None |
| Visitors in hospitals and nursing homes | I-2 | 1 per 75 | 1 per 100 | None | 1 per 500 | None |
| Prisons | I-3 | 1 per cell | 1 per cell | 1 per 15 | 1 per 100 | 1 service sink |
| Reformatories, detention and correctional centers | I-3 | 1 per 15 | 1 per 15 | 1 per 15 | 1 per 100 | 1 service sink |
| Adult day care and child day care | I-4 or E | 1 per 15 | 1 per 15 | 1 | 1 per 100 | 1 service sink |
| Retail stores, service stations, shops, salesrooms, markets and shopping centers | M | 1 per 500 | 1 per 750 | None | 1 per 1,000 | 1 service sink (not required at 15 or fewer occupants) |
| Hotels, motels and transient boarding houses | R-1 | 1 per sleeping unit | 1 per sleeping unit | 1 per sleeping unit | None | 1 service sink |
| Dormitories, fraternities, sororities and non-transient boarding houses | R-2 | 1 per 10 | 1 per 10 | 1 per 8 | 1 per 100 | 1 service sink |
| Apartment houses | R-2 | 1 per dwelling unit | 1 per dwelling unit | 1 per dwelling unit | None | 1 kitchen sink per unit; 1 clothes washer connection per 20 units |
| Congregate living facilities with 16 or fewer persons | R-3 | 1 per 10 | 1 per 10 | 1 per 8 | 1 per 100 | 1 service sink |
| One- and two-family dwellings and lodging houses with five or fewer guestrooms | R-3 | 1 per dwelling unit | 1 per dwelling unit | 1 per dwelling unit | None | 1 kitchen sink and 1 clothes washer connection per unit |
| Warehouses, storehouses and freight depots, low and moderate hazard | S-1, S-2 | 1 per 100 | 1 per 100 | None | 1 per 1,000 | 1 service sink |
Table footnotes that change the count: employee toilets in prisons, detention centers and care facilities are separate from those for inmates or care recipients (b); one single-occupant toilet room may serve two adjacent patient sleeping units (c); seasonal outdoor seating counts toward the occupant load (d); outdoor public swimming pools follow Section 609 of the International Swimming Pool and Spa Code (f).
Rules that modify the Table 403.1 count
| Rule | IPC 2021 section | Effect on the count |
|---|---|---|
| Single-user and family or assisted-use rooms | 403.1.2 | Their fixtures count toward the total; rooms must be identified for use by all persons |
| Lavatory distribution | 403.1.3 | With two or more toilet rooms per sex, lavatories are distributed in proportion to water closets |
| Group wash fixtures | 419.1 | Every 20 inches of rim counts as one lavatory |
| Urinals | 424.2 | Replace not more than 67 percent of required water closets in assembly and educational rooms, 50 percent elsewhere |
| Drinking fountains, small occupancies | 410.2 | Not required for an occupant load of 15 or fewer |
| Drinking fountains, substitution | 410.4 | Not required in restaurants serving free water in a container; water dispensers may replace up to 50 percent where three or more fountains are required |
| High and low fountains | 410.3.1 | Where fountains are provided, at least two: one for wheelchair users and one for standing persons, or one fountain with both spouts |
| Fountain location | 403.5, 410.5 | Within 500 feet and one story of a tenant (300 feet in malls); never inside a public restroom |
| Service sinks in malls | 403.6 | A shared service sink within 300 feet and one story may serve mall tenants |
| Fixture clearances | 405.3.1 | 15 inches centerline to side wall, 30 inches between fixtures, 21 inches in front; compartments 30 by 60 inches (30 by 56 inches for wall-hung water closets) |
Where can you explore related guidance?
- Explore all design standards guidance
- ADA Restroom Dimensions & Clearances (Typical Minimums)
- IBC Occupancy Classifications: Groups A, B, E, F, H, I, M, R, S & U
- Traps, Interceptors and Separators: IPC Chapter 10 Requirements
- Plumbing Fixture Count Calculator: IBC Table 2902.1 Method
- Occupant Load Calculator: IBC Method, Factors and Worked Example
- Plumbing Fixture: Building Code Definition
Sources and method
Fixture ratios, calculation rules and exceptions are taken from the 2021 International Plumbing Code, Chapter 4, Fixtures, Faucets and Fixture Fittings (Table 403.1 and Sections 403, 405, 410, 419 and 424). Dwelling requirements come from 2021 International Residential Code Chapter 3 (Section R306) and Chapter 27, Plumbing Fixtures (Section P2705). The restaurant occupant load uses the IBC 2021 Table 1004.5 factor for unconcentrated assembly. Section numbering follows the 2021 editions; these are typical model-code values, so verify every ratio and exception against the edition adopted by the authority having jurisdiction, any state plumbing code (some states adopt the Uniform Plumbing Code instead) and local amendments.
Source links
Frequently asked questions
How do you calculate the number of toilets a building needs?
Take the occupant load from the IBC, divide it in half for each sex, divide each half by the Table 403.1 ratio for the use and round up. A 160-seat restaurant has 80 occupants per sex; at 1 per 75 that is 1.07, so 2 water closets per sex. Add drinking fountains and a service sink from the same row.
When is a single unisex restroom allowed instead of separate men's and women's rooms?
IPC Section 403.2 allows one shared facility where the total occupant load, employees and customers combined, is 15 or fewer, in mercantile spaces of 100 or fewer and business spaces of 25 or fewer. Single-user rooms and all-gender multi-user rooms with enclosed water closet compartments are also permitted in place of separate facilities.
Do single-user restrooms count toward the required fixtures?
Yes. Section 403.1.2 counts fixtures in single-user, family and assisted-use toilet rooms toward the total, provided the rooms are identified as available to everyone regardless of sex. Where each sex would need only one water closet, two family or assisted-use rooms can serve as the required separate facilities under Section 403.2.1.
When is a drinking fountain required?
Table 403.1 gives a ratio for most uses, such as 1 per 100 in offices and schools and 1 per 1,000 in retail stores. Section 410.2 waives fountains for 15 or fewer occupants, restaurants that serve free water in a container need none, and water dispensers can replace half of the fountains where three or more are required.
Is a service sink required in every building?
Most rows of Table 403.1 require one service sink. Footnote e removes it for business and mercantile spaces with an occupant load of 15 or fewer, hospitals need one per floor, and dwelling rows require a kitchen sink instead. Mall tenants may share a service sink within 300 feet under Section 403.6.
What plumbing fixtures does a house need under the IRC?
IRC Section R306 requires every dwelling unit to have a water closet, a lavatory, a bathtub or shower and a kitchen sink, connected to an approved sewer and water supply with hot and cold water. Section P2705.1 adds the layout clearances: 15 inches to a side wall, 30 inches between fixtures and 21 inches in front.
Related pages
- IBC Occupancy Classifications: Groups A, B, E, F, H, I, M, R, S & U
Every IBC occupancy group and subgroup, A-1 to U: church A-3, restaurant A-2, hotel R-1, warehouse S-1/S-2, plus Section 508 mixed occupancy rules.
- Mechanical Exhaust Requirements: Bathroom, Kitchen and Dryer Exhaust (IRC and IMC)
Bathroom fan 50 cfm or 20 continuous, kitchen 100 cfm, 35-ft dryer duct limit with elbow deductions, IMC Table 403.3.1.1 exhaust rates and exhaust termination clearances.
- Minimum Ceiling Height Requirements (IBC & IRC)
IRC R305.1 and IBC 1208.2 minimum ceiling heights for habitable rooms, bathrooms, corridors, basements and sloped ceilings, with section numbers.
- IBC Stair Code vs. IRC: Riser, Tread, Headroom & Width
IBC stair code at a glance with section numbers, plus IRC equivalents for riser, tread, headroom, width, nosing and handrails, and 2018 to 2024 changes.
- Storm Drainage Sizing: Roof Drains, Leaders and Secondary Drains (IPC Chapter 11)
IPC Chapter 11 roof drain and leader sizing: gpm = 0.0104 x rainfall x roof area, storm pipe capacity tables, roof area per leader at 1-5 in/h, and secondary drain rules.
- Traps, Interceptors and Separators: IPC Chapter 10 Requirements
IPC Chapter 10 trap rules: 2 to 4 inch trap seal, 24/30 inch trap distance, banned S and drum traps, trap sizes by fixture, grease interceptor and oil separator sizing.