Building performance

Mass timber char depth calculator

Work out char depth, effective char depth and the residual section of glulam, timber and CLT after a fire exposure, by NDS or Eurocode 5.

Free to use & exportNo signupLocal processingImperial & metric

Loading the local tool…

What a timber char depth calculator does

Exposed mass timber resists fire by charring at a predictable rate. The char layer insulates the wood behind it, so a beam, column or CLT panel keeps a residual core that can still carry load. This calculator works out how deep the char goes after a given fire exposure, adds the allowance for heat-weakened wood, and reports the residual dimensions and how much of the area, section modulus and stiffness remains.

Two published methods are built in. NDS Chapter 16, explained in AWC Technical Report 10, uses a nominal char rate of 1.5 in/h, a non-linear char depth a_char = βn × t^0.813, and an effective char depth 20 % deeper; for CLT it lets each lamination fall off when the char front reaches its glueline. EN 1995-1-2 multiplies a design charring rate from its Table 3.1 by time and adds a 7 mm zero-strength layer. Imperial defaults to NDS and metric to EN 1995-1-2; you can use either in either unit system.

The result is a section, not a fire rating. Whether the residual member carries its load in fire depends on the design load, the fire design adjustment factors, connections and any protection, which the method's structural checks and the engineer of record cover.

How to use the mass timber char depth calculator

  1. Choose Imperial or Metric. Imperial starts with the NDS method and an 8¾ × 24 in glulam beam; metric starts with EN 1995-1-2 and a 240 × 600 mm beam.
  2. Pick the Method and the Member: a beam or column, a CLT panel, or a solid panel such as NLT, DLT or GLT charred from one face.
  3. Enter the Fire exposure time (min), usually the required fire-resistance rating: 60, 90 or 120 minutes.
  4. For a beam or column, choose the Exposed sides and enter the Member width and Member depth. For a panel, enter the Panel thickness, and for CLT the CLT lamination thickness.
  5. For EN 1995-1-2, choose the Timber product (EN 1995-1-2 Table 3.1) or enter custom rates. For NDS, keep the Nominal char rate βn at 1.5 in/h unless your product data give another value.
  6. Read the char depth, the effective char depth, the residual dimensions and the percentages retained, then download the PDF, CSV or the SVG section diagram.

Worked example

Imperial: An 8¾ × 24 in glulam beam exposed on three sides for one hour chars 1.5 in (a_eff 1.8 in) by NDS Chapter 16, leaving 5.15 × 22.2 in: 54.4% of the area and 50.4% of the section modulus.

Metric: A 240 × 600 mm softwood glulam beam exposed on three sides for 60 minutes chars 42 mm (d_ef 49 mm) by EN 1995-1-2, leaving 142 × 551 mm: 54.3% of the area and 49.9% of the section modulus.

Char depth and effective char depth (NDS Chapter 16)

NDS Chapter 16 uses a non-linear char model because charring slows as the insulating char layer thickens. With βn = 1.5 in/h for sawn lumber, glulam, structural composite lumber and CLT, the char depth after t hours is a_char = 1.5 × t^0.813 in. The effective char depth adds 20 % for the zone of heated, weakened wood and corner rounding: a_eff = 1.2 × a_char. Each exposed face loses a_eff, so a beam exposed on three sides loses 2 × a_eff from its width and a_eff from its depth.

IBC Section 722 points to NDS Chapter 16 for calculating the fire resistance of exposed wood members, so these are the depths most US mass timber designs start from.

NDS char depths for βn = 1.5 in/h (AWC TR 10 Table 4.1.1.4A)
Required fire resistanceChar depth, a_charEffective char depth, a_eff
1 hour1.5 in (38 mm)1.8 in (46 mm)
1½ hours2.1 in (53 mm)2.5 in (64 mm)
2 hours2.6 in (67 mm)3.2 in (80 mm)

Charring rates in EN 1995-1-2 (Eurocode 5)

EN 1995-1-2 gives two design charring rates. β0 is the one-dimensional rate for a face with no exposed corners, such as a slab soffit. βn is a larger notional rate that folds in the corner rounding of a beam or column exposed on three or four sides. The reduced cross-section method then adds a zero-strength layer k0 × d0, with d0 = 7 mm and k0 rising from 0 to 1 over the first 20 minutes, so d_ef = βn × t + 7 mm for any exposure of 20 minutes or more.

The second-generation revision of EN 1995-1-2 changes several of these values and adds rules for CLT; the calculator uses the 2004 edition.

EN 1995-1-2 Table 3.1 rates and effective char depth d_ef = d_char + 7 mm
Productβ0 (mm/min)βn (mm/min)d_ef at 60 mind_ef at 90 min
Softwood glulam (ρk ≥ 290 kg/m³)0.650.7049 mm70 mm
Softwood solid timber (ρk ≥ 290 kg/m³)0.650.8055 mm79 mm
Hardwood (ρk ≥ 450 kg/m³)0.500.5540 mm56.5 mm
LVL (ρk ≥ 480 kg/m³)0.650.7049 mm70 mm
Any of the above, one face, no corners (β0 0.65)0.65—46 mm65.5 mm

CLT char depth and lamination fall-off

Full-scale fire tests of CLT showed char layers falling away as the char front approached a glueline, exposing fresh wood that then charred quickly again. AWC TR 10 models this with the time to reach each glueline, t_gi = (h_lam ÷ βt)^1.23 hours, the number of laminations that fall off, n_lam = t ÷ t_gi rounded down, and a_char = n_lam × h_lam + βt × (t − n_lam × t_gi)^0.813. Thinner laminations fall off sooner, so they char deeper.

PRG 320-2018 added an elevated-temperature adhesive test intended to stop this fall-off, but the stepped model remains the conservative NDS approach. The thickness retained is not a strength ratio for CLT: which layers remain, and whether they run parallel to the span, decides the residual capacity.

CLT effective char depth a_eff, βn = 1.5 in/h (AWC TR 10 Table 4.1.1.4B)
Lamination thickness1 hour1½ hours2 hours
¾ in2.2 in3.2 in4.3 in
1 in2.0 in3.0 in4.0 in
1⅜ in (35 mm)1.9 in2.8 in3.8 in
1½ in1.8 in2.8 in3.6 in
2 in1.8 in2.6 in3.6 in

Worked example: a glulam beam exposed on three sides

Take an 8¾ × 24 in glulam beam exposed on its soffit and both sides for one hour under NDS. a_char = 1.5 × 1^0.813 = 1.5 in and a_eff = 1.8 in. The residual width is 8.75 − 2 × 1.8 = 5.15 in and the residual depth 24 − 1.8 = 22.2 in, so 54.4 % of the area, 50.4 % of the section modulus and 46.6 % of the moment of inertia remain.

In metric with EN 1995-1-2, a 240 × 600 mm softwood glulam beam for 60 minutes chars 0.70 × 60 = 42 mm, and d_ef = 42 + 7 = 49 mm. The residual section is 142 × 551 mm: 54.3 % of the area and 49.9 % of the section modulus. The structural fire check then compares that residual section, with fire-design strength factors, against the load present during the fire.

Who it is for and when to use it

Sizing exposed mass timber

See how much larger a beam, column or panel must be to keep enough section after a 1- or 2-hour exposure, before the engineer runs the fire design.

Comparing CLT layups

Check how lamination thickness and fall-off change the char depth and how many layers remain after a rated exposure.

Explaining fire performance to clients

Show a residual section diagram to explain why a heavy timber member can be left exposed in a rated building.

Cross-checking NDS and Eurocode results

Run the same member through both methods to understand why international projects get different sizes.

Method, formulas & assumptions

NDS Chapter 16 (AWC TR 10): a_char = βn × t^0.813 (βn = 1.5 in/h, t in hours), a_eff = 1.2 × a_char; for CLT with equal laminations, t_gi = (h_lam ÷ βn)^1.23, n_lam = ⌊t ÷ t_gi⌋ and a_char = n_lam × h_lam + βn × (t − n_lam × t_gi)^0.813. EN 1995-1-2: d_char = βn × t with exposed corners (3 or 4 sides) or β0 × t without (Table 3.1 rates), d_ef = d_char + k0 × 7 mm, k0 = min(1, t ÷ 20 min). Each exposed face loses the effective depth; area, strong-axis section modulus and moment of inertia retained are ratios of the residual to the original rectangle.

Imperial inputs are converted with exact factors (1 ft = 0.3048 m, 1 lb = 0.45359237 kg, 1 US gal = 3.785411784 L) before the calculation runs in SI, then results are converted back.

Common mistakes to avoid

  • Using the char depth instead of the effective char depth. The extra heated-zone allowance (20 % in NDS, 7 mm in EN 1995-1-2) must come off the section too.
  • Forgetting exposed faces. A beam that looks protected on top may be exposed if the deck above is not continuous or gaps are not sealed.
  • Treating CLT thickness retained as strength retained. Cross layers carry little bending; model the remaining layup.
  • Mixing methods: applying EN charring rates with NDS strength factors, or the reverse.
  • Ignoring connections. Steel plates and fasteners usually need more cover or protection than the member itself.

Scope & limits

Section properties only: it does not check load capacity in fire, connections, gypsum or encapsulation protection, or the fire-resistance rating, which need the method's structural fire design or a tested assembly. EN 1995-1-2:2004 has no CLT fall-off rule, so CLT is charred one-dimensionally under that method. Rates are published design values for unprotected members; product approvals and the engineer of record govern.

Frequently asked questions

What is the char rate of wood?

NDS Chapter 16 uses a nominal char rate of 1.5 in/h (about 0.64 mm/min) for sawn lumber, glulam, SCL and CLT, applied non-linearly. EN 1995-1-2 uses design rates of 0.65 mm/min one-dimensionally and 0.70 to 0.80 mm/min notionally for softwood.

How deep does glulam char in one hour?

Under NDS, the char depth is 1.5 in and the effective char depth 1.8 in per exposed face. Under EN 1995-1-2, softwood glulam exposed on three or four sides gives 42 mm of char and an effective depth of 49 mm.

What is the difference between char depth and effective char depth?

Char depth is the wood actually turned to char. Effective char depth adds the layer just behind the char that is too hot to count on for strength and stiffness: 20 % of the char depth in NDS, or a 7 mm zero-strength layer in EN 1995-1-2.

Does CLT char faster than glulam?

The char rate is the same, but laminations can fall off when the char front reaches a glueline, which exposes fresh wood. The NDS stepped model gives a slightly deeper char for CLT, especially with thin laminations and longer exposures.

How big does a timber beam need to be for a 2-hour rating?

Under NDS, each exposed face loses an effective 3.2 in, so a beam exposed on three sides loses 6.4 in of width and 3.2 in of depth before the residual section is checked for strength. A beam narrower than 6.4 in has nothing left, which is why two-hour exposed members are usually 8¾ in wide or more.

Which method should I use?

Use the method your building code adopts: NDS Chapter 16 for US projects under the IBC, EN 1995-1-2 with the national annex in Europe, and CSA O86 Annex B in Canada, which this tool does not implement.

Does this tool give a fire-resistance rating?

No. It calculates the residual section. A rating needs the structural fire check of that section under load, connection design and any protection, or a tested assembly.

Do I need an account to download the result?

No. All calculations, local file processing and exports on this page are free, without an account.

Where are my inputs stored?

The tool keeps inputs in this browser tab. It does not upload them or create a cloud copy. Save or download anything you want to keep before leaving the page. Standard site analytics may operate independently of the tool.

Can I work in metric instead of imperial?

Yes. Use the Imperial / Metric switch above the inputs. Imperial (feet, inches, pounds, gallons) is the default; switching converts every dimensional field and result, and your choice is remembered across the free tools in this browser.