Bathroom fixture clearance checker

Check toilet, vanity, double basin and shower clearances against the IRC minimum, NKBA recommendations or ADA 2010, with the margin on every check.

Free to use & exportNo signupLocal processingImperial & metric

Loading the local tool…

How much space a toilet, vanity and shower need

The US model residential code, the IRC, needs 15 in (381 mm) from the centre of a toilet to any side wall or obstruction, 21 in (533 mm) of clear space in front of a toilet or vanity, 24 in (610 mm) in front of a shower opening, and a shower of at least 900 in² with no side under 30 in. The National Kitchen & Bath Association recommends more for comfort: 18 in to the toilet centreline, 30 in in front of every fixture and a 36 × 36 in shower.

This checker takes the clearances you measure on a plan or on site and compares each one with the standard you choose: the IRC minimum, NKBA recommendations or the 2010 ADA Standards for an accessible bathroom. It reports a verdict, the number of checks that fail, the margin on every check and what to change, such as how far to move the toilet. The chart shows which clearances have room to spare and which are short.

The numbers are the model documents' figures. Your jurisdiction may have adopted a different edition or amendments, the Uniform Plumbing Code applies in some states, and other countries use different rules.

How to use the bathroom fixture clearance checker

  1. Choose Imperial or Metric. Every clearance switches between inches and millimetres.
  2. Choose what to Check against: IRC minimum, NKBA recommended or ADA 2010 accessible.
  3. Enter the Toilet centreline to left wall or obstruction and Toilet centreline to right wall or obstruction, measured from the centre of the bowl to the nearest wall, vanity, tub or fixture on each side.
  4. For the IRC or NKBA, enter the Clear space in front of toilet. For ADA, enter the Clear depth from wall behind toilet instead.
  5. Enter the Clear space in front of vanity, and for the IRC or NKBA the Basin centreline to side wall and, for a double vanity, the Double vanity: basin centre to centre. For ADA, enter the Knee and toe space under basin.
  6. Enter the Shower interior width and Shower interior depth to the finished walls or glass (0 for both if there is no shower) and the Clear space in front of shower entry.
  7. Choose whether the Bathroom door swings clear of every fixture clearance or into one.
  8. Read the verdict, the table of checks and the margin chart, then download the PDF, CSV or SVG, or copy the result.

Worked example

Imperial: A toilet 16 in and 21 in from its side obstructions with 26 in in front, a vanity with 26 in in front and a 36 × 32 in shower (1,152 in²) with 30 in in front meet the IRC minimum, with 1 in to spare beside the toilet. Against NKBA recommendations five checks fall short, and the toilet should move 2 in to the right.

Metric: A toilet 410 mm and 530 mm from its side obstructions with 660 mm in front, a vanity with 660 mm in front and a 910 × 810 mm shower (0.737 m²) with 800 mm in front meet the IRC minimum, with 29 mm to spare beside the toilet. Against NKBA recommendations, five checks fall short.

Toilet clearance requirements

Side clearance is measured from the centreline of the toilet, so a toilet between two walls needs at least 30 in (762 mm) between them under the IRC, and 36 in for NKBA's recommended 18 in each side. Front clearance runs from the front of the bowl to the nearest wall, fixture or door.

The ADA measures differently. The toilet sits 16 to 18 in from a side wall that carries the grab bars, and a clear floor area 60 in wide from that wall and 56 in deep from the wall behind contains the toilet itself, so the calculator asks for the depth from the rear wall instead of the space in front of the bowl.

Toilet clearances by standard
ClearanceIRC minimumNKBA recommendedADA 2010
Centreline to side wall or obstruction15 in (381 mm)18 in (457 mm)16–18 in to the side wall (604.2)
Clear space in front21 in (533 mm)30 in (762 mm)60 × 56 in from side and rear walls (604.3.1)
Between adjacent fixtures, centre to centre30 in (762 mm)18 in to the neighbouring fixture's centrelineNo other fixture within the clearance

Minimum shower size

The IRC (P2708.1) asks for at least 900 in² (0.58 m²) of finished interior area with no dimension under 30 in, so 30 × 30 in is the smallest square shower. A narrower shower down to 25 in is allowed if it has at least 1,300 in², which the calculator applies automatically. NKBA recommends 36 × 36 in as a comfortable minimum.

Measure inside the finished walls or glass. A thick tile and backer board build-up can take a nominal 32 in base below the 30 in minimum.

Shower interior size and clearance in front
StandardMinimum interiorClear in front of entry
IRC minimum900 in² and 30 in minimum (or 1,300 in² and 25 in)24 in (610 mm)
NKBA recommended36 × 36 in (914 × 914 mm)30 in (762 mm)
ADA roll-in shower30 × 60 in (760 × 1,525 mm)30 in deep × 60 in wide
ADA transfer showerExactly 36 × 36 in36 × 48 in

Vanity, basin and double sink spacing

The IRC treats a lavatory like a toilet: 15 in from its centreline to a side wall or obstruction, 30 in centre to centre between adjacent fixtures and 21 in clear in front. Some jurisdictions read the side clearance as applying only to free-standing basins, so check locally if a vanity basin sits close to a wall. NKBA recommends 20 in to the side wall, 36 in between two basins and 30 in in front.

For a 60 in double vanity, the basins usually sit about 30 in apart, which meets the IRC but not the NKBA recommendation; a 72 in vanity gives room for 36 in.

Lavatory and vanity clearances
ClearanceIRC minimumNKBA recommendedADA 2010
Basin centreline to side wall15 in (381 mm)20 in (508 mm)—
Double basins, centre to centre30 in (762 mm)36 in (914 mm)—
Clear space in front21 in (533 mm)30 in (762 mm)30 × 48 in forward approach, up to 25 in under the basin

Worked example: a code-minimum bathroom against NKBA

A toilet sits 16 in from the wall on its left and 21 in from the vanity on its right, with 26 in in front of the bowl. The vanity has 26 in in front and its basin centreline is 18 in from the wall; the shower is 36 × 32 in inside, 1,152 in², with 30 in in front. Against the IRC, every check passes, and the tightest margin is the 1 in beside the toilet.

Switch to NKBA recommended and five checks fall short: the toilet's left side by 2 in, the space in front of the toilet and vanity by 4 in each, the basin centreline by 2 in and the shower's 32 in side by 4 in. The calculator suggests moving the toilet 2 in to the right, which still leaves 19 in on that side.

Who it is for and when to use it

Checking a remodel layout before plumbing moves

Confirm the toilet and shower positions meet code before the drain and supply lines are set, when moving them is still cheap.

Choosing between code minimum and comfort

Run the same layout against the IRC and NKBA to see which clearances are tight and where a few inches buy a more comfortable room.

Planning an accessible or ageing-in-place bathroom

Check toilet, basin and roll-in shower clearances against the 2010 ADA Standards as a benchmark.

Reviewing a contractor's or designer's plan

Measure the drawing and get a margin for every clearance, with the shortfalls listed.

Method, formulas & assumptions

Each measured clearance is compared with the selected standard, margin = actual − required. IRC (2021 R307.1, Figure R307.1, P2705.1, P2708.1): toilet and basin centreline ≥ 15 in (381 mm) to a side wall or obstruction, adjacent basins ≥ 30 in centre to centre, ≥ 21 in (533 mm) clear in front of a toilet or lavatory, ≥ 24 in (610 mm) in front of a shower opening, shower ≥ 900 in² with a 30 in minimum dimension (or 1,300 in² with 25 in). NKBA recommended: toilet centreline 18 in, 30 in in front of toilet, vanity and shower, basin centreline 20 in from a wall, basins 36 in apart, shower 36 × 36 in. ADA 2010: toilet centreline 16–18 in from the side wall (604.2), clearance 60 in wide from the side wall × 56 in deep from the rear wall (604.3.1), 48 in forward-approach depth at the basin with up to 25 in of knee space counted (305), roll-in shower 30 × 60 in with 30 in clear in front (608.2.2), no door swing into a fixture clearance (603.2.3).

Imperial inputs are converted with exact factors (1 ft = 0.3048 m, 1 lb = 0.45359237 kg, 1 US gal = 3.785411784 L) before the calculation runs in SI, then results are converted back.

Common mistakes to avoid

  • Measuring the toilet side clearance from the edge of the tank or bowl. The rule runs from the centreline.
  • Measuring the shower to the base or rough framing. Use the finished inside faces of the walls or glass.
  • Forgetting the door. The IRC measures the front clearance to a door, and NKBA and the ADA want doors to swing clear of fixture clearances.
  • Ignoring a vanity or tub as an obstruction. The 15 in side clearance applies to any wall, partition, vanity or other fixture.
  • Assuming the IRC applies everywhere. Some states use the UPC, local amendments change figures, and outside the US the national code governs.
  • Treating ADA numbers as a home requirement. They apply to public facilities and covered accessible units, though they are a useful benchmark for accessible homes.

Scope & limits

Checks the clearances you measure; it does not draw or lay out the room. IRC values are the 2021 model code: confirm the edition and amendments your jurisdiction adopted, and the plumbing code where the UPC applies. NKBA values are best-practice recommendations. ADA checks cover toilet, basin and roll-in shower clearances and door swing only, not grab bars, heights, turning space, reach ranges or controls. UK, Australian, New Zealand and other national codes use different figures.

Frequently asked questions

How much space do you need around a toilet?

The IRC needs at least 15 in (381 mm) from the toilet's centreline to any side wall or obstruction, so 30 in between side walls, and 21 in (533 mm) clear in front. NKBA recommends 18 in each side and 30 in in front.

What is the minimum shower size?

Under the IRC, a shower needs at least 900 in² of interior area with no dimension under 30 in, so 30 × 30 in is the minimum square shower. NKBA recommends 36 × 36 in, and an ADA roll-in shower is at least 30 × 60 in.

How much space do you need in front of a vanity?

At least 21 in (533 mm) under the IRC, measured from the front of the vanity to the nearest wall, fixture or door. NKBA recommends 30 in (762 mm).

How far apart should double sinks be?

The IRC needs at least 30 in (762 mm) between the centrelines of adjacent fixtures. NKBA recommends 36 in (914 mm) between two basins.

How much clearance do you need in front of a shower?

The IRC's fixture clearance figure shows 24 in (610 mm) in front of the shower opening. NKBA recommends 30 in (762 mm), and an ADA roll-in shower needs a 30 in deep by 60 in wide clear space.

Can a bathroom door swing into the toilet clearance?

The IRC measures the 21 in front clearance to any wall, fixture or door, so the door must not cut into it. NKBA recommends doors not interfere with fixtures, and ADA 603.2.3 does not allow a door to swing into a fixture's clear floor space except in a single-user room with clear floor space beyond the swing.

How far is a toilet from the wall behind it?

The usual rough-in is 12 in from the finished back wall to the centre of the drain flange; 10 in and 14 in toilets are also made for other rough-ins.

Do ADA bathroom rules apply to my house?

Usually not. The ADA Standards apply to public accommodations and some housing, such as accessible units in covered multifamily buildings. They are a good benchmark for an accessible or ageing-in-place home.

Do I need an account to download the result?

No. All calculations, local file processing and exports on this page are free, without an account.

Where are my inputs stored?

The tool keeps inputs in this browser tab. It does not upload them or create a cloud copy. Save or download anything you want to keep before leaving the page. Standard site analytics may operate independently of the tool.

Can I work in metric instead of imperial?

Yes. Use the Imperial / Metric switch above the inputs. Imperial (feet, inches, pounds, gallons) is the default; switching converts every dimensional field and result, and your choice is remembered across the free tools in this browser.

Further reading

In this category

Explore the room at eye level before anything is ordered.

Place furniture, fittings and lighting from Harth's object library, walk through the room in 3D and render it for your client, starting from a model you've already drawn. Downloaded results are yours to take with you.